6
Startup
Parameter description
Operating Instructions – CMP ELVCD
71
Parameters
P830.0
–
P840.0
define the fault responses for the following faults.
Para-
meter
Fault
Factory set-
ting
Bit
Adjustable
responses
1)
P830.0
Motor overtemperature 3: Immediate
stop
Bit 2
0: No response
=> "114" = 0 and "116" = 0
1: Display warning
=> "114" = 1 and "116" = 0
2: Rapid stop
=> "114" = 0 and "116" = 1
3: Immediate stop
=> "114" = 1 and "116" = 1
P831.0
Undertemperature/
overtemperature of the
power electronics
3: Immediate
stop
Bit 3
P832.0
DC link
undervoltage
3: Immediate
stop
Bit
13
P833.0
I
2
t motor fault
(I
2
t at 100%)
1: Display
warning
Bit
18
P834.0
I
2
t controller fault
(I
2
t at 100%)
1: Display
warning
Bit
19
P835.0
I
2
t at 80%
1: Display
warning
Bit
25
P836.0
Motor temperature
5 °C below maximum
limit
3: Immediate
stop
Bit
26
P837.0
Output stage tempera-
ture
5 °C below maximum
limit
3: Immediate
stop
Bit
27
P838.0
Lag error
monitoring
3: Immediate
stop
Bit
28
P839.0
Limit switch fault
3: Immediate
stop
Bit
30
P840.0
CAN communication
error
3: Immediate
stop
Bit
22
0: No response
=> "115" = 0 and "117" = 0
1: Display warning
=> "115" = 1 and "117" = 0
2: Rapid stop
=> "115" = 0 and "117" = 1
3: Immediate stop
=> "115" = 1 and "117" = 1
1) The response is set by parameter indexes "114" – "117".
Parameter 886.0
CAN address
This parameter indicates the current CAN address of the drive. The address is set in
MultiMotion.
Parameter 887.0
CAN active
The parameter defines whether CAN bus is set to active.
22759468/EN – 11/2017