5
Electrical installation
CAN bus
Operating Instructions – CMP ELVCD
29
Cable
Length/installation
type
Component
1 m: Part number 19111614
2 m: Part number 19111630
3 m: Part number 13301322
5 m: Part number 13295810
10 m: Part number 19129270
15 m: Part number 19129289
M12, female, A-coded ↔ Open
Fixed length
MOVI‑PLC
®
5.6.3
Connection of cables with open end
The following table shows the core assignments of the cables with an open end and
the assignments of the CAN bus interface at the MOVI-PLC
®
controller.
Connection cable
MOVI-PLC
®
X32 (CAN 2)/X33 (CAN 1)
X26
(CAN 1)
Signal name
Core color
No.
Terminating resistor connec-
tion
No.
CAN_GND
Black
1
3
CAN_H
White
2
x
1
CAN_L
Blue
3
x
2
•
The CAN 2 system bus is galvanically isolated. The ELVCD drive should prefer-
ably be connected to the CAN 2 (X32) interface.
•
The CAN 1 system bus is not galvanically isolated.
•
The pins of plug connectors X33 and X26 are jumpered internally in accordance
with the table. When the ELVCD drive is connected to X26 (CAN 1), connect the
terminating resistor to the pins of plug connector X33 which are marked with an "x"
in the table above.
•
Ensure that you do not combine the CANopen bus stations (e.g. the ELVCD drive)
with MOVILINK
®
bus stations on a bus. However, if this is necessary, please con-
tact SEW‑EURODRIVE.
5.6.4
Connection cables with right-angle connectors
Connection cables with right-angle connectors can be purchased from specialist elec-
trical retailers (e.g. PHOENIX CONTACT).
22759468/EN – 11/2017