Chapter 6: Maintenance
225
Be sure you set the fan on the mounting pins, as shown above.
Be sure the fans point outward, towards the handle (above).
11. Place the top section of the cooling unit onto the bottom section and slide the
top lock it in place.
12. Tighten the thumbscrew.
13. If there is a battery on the cooling unit, reattach the battery connector.
14. Carefully slide the cooling unit into the enclosure.
15. Gently press the handle in and upward until it locks.
16. Verify that the Fan LEDs are green.
This completes the fan replacement procedure.