External Input Signal (Used for both DIN and Remote Reset Input)
• General Purpose Input (DIN) level must be 1.5S or longer to be
detected.
• Be sure the voltage value between terminals is controlled via
the input voltage, so that the PL is operated within its recom-
mended range. If the input voltage exceeds this range, a mal-
function or PL damage may occur.
• With Sink/Source input, even if the D(-), and RESET(-) are posi-
tive, and D(+), RESET(+) are negative, no problems are created.
Be sure to operate the unit within the recommended voltage
range.
For detailed connector wiring information,
2.3.5 RAS Interface (RAS)
Input Voltage
DC12V to DC24V
Input Current
7mA
Operating Current
ON Voltage: 9V (min.), OFF Voltage: 3V (max.)
Insulation Method
Via Photocoupler
(Interface Circuit)
(Connection Example)
Cable
No polarity -
for Sink/Source input
Reset Input(+)pin 5
DIN0(+)pin 6
DIN1(+)pin 13
(DC12 to DC24V)
R
PC357
Reset Input(-)pin 11
DIN0(-)pin 12
DIN1(-)pin 24
D-sub 25 pin Connector
+5V
1.8k
1/8W
1.8k
1/8W
R
DC12 to DC24V
Switch or
switching device