PL-5910 Series User Manual
9-8
O: Can be set
X: Cannot be set
Ite m
Ope ra tion
Ala rm Output
RAS Interface Alarm Output (#9 to #10) signal is output.
Power LED turns orange.
La m p Output
RAS Interface Alarm Output (#21 to #22) signal is output.
Buzze r
Buzzer sound is output as an alarm notification. (except for when the
OS Shutdown feature is checked)
Popup Me ssa ge
Error message appears as a Pop-Up Message Screen (on the PL unit's
screen)
OS Shutdow n
Shuts down the PL unit's OS. T his can be set to either display a
shutdown confirmation message, or perform a forced OS
shutdown.Default is display a shutdown confirmation message.
Re se t
Resets the PL unit by performing a forced shutdown.
Ena ble
Allows setting of monitoring items.
*1 When setting Enable on Remote Reset, the same action as the Reset occurs.
Performing reset without first shutting down the PL unit's OS may destroy the PL
unit's file data system.
Each of the above items performs the following operation.
The following chart shows the features available when any of the monitoring value
ranges set in the [PC Health Status] menu is exceeded.
9.2.2
System Monitor Property Settings (PL_Wps.exe)
Enable
Alarm
Output
Lamp
Output
Buzzer
Popup
Message
OS
Shutdown
OS
Restart
*1
Time
Out
Watchdog Timer
O
O
O
O
O
O
O
O
Voltage
O
O
O
O
O
O
X
X
Temperature
O
O
O
O
O
O
X
X
UniversalIn0
O
O
O
O
O
O
X
X
UniversalIn1
O
O
O
O
O
O
X
X
Backlight
O
O
O
O
O
X
X
X
Remote Reset
O
X
X
X
X
X
X
X