External Output Signal (DOUT, Alarm Output, Lamp Output Port)
External Power Output
+5V
:100mA (MAX)
+12V
:100mA (MAX)
• Be sure to operate the unit within its maximum load current. If
the maximum load current exceeds this range, a malfunction or
PL damage may occur.
• Design your electrical system by adding the load current and
voltage values to the terminal voltage. If load current value used
is large, a maximum voltage of 1.5V will exist between the terminals.
• When connecting an induction load, be sure to connect the
above drawing's protection diode(*1).
Rated Load Voltage
DC12V to DC24V
Maximum Load Current
100mA/point
Maximum Voltage Drop between T erminals
1.5V (at 100mA load current)
Isolation Method
Via photocoupler
For detailed connector wiring information,
2.3.5 RAS Interface (RAS)
(Interface Ciruit)
Connection Example
Cable
R
PC357
Dsub 25 pin connector
4.7k
Ω
SSTA06
DOUT(-) pin 7
Alarm Output(-) pin 9
Lamp Output(-) pin 21
DOUT(+) pin 8
Alarm ) pin 10
Lamp ) pin 22
+5V
DC12V to
DC24V
Load
*1