Note the following guidelines for installing the ITS within a routed ICN topology:
• An ITS subnet can be connected up to 22 ICN Database Domains via routers.
• Up to 320 ITS Standard Access Points may be installed on a routed ICN
topology.
• Up to 320 ITS Core Access Points and up to 640 Remote Antennas (i.e., two per
Core AP) may be installed on a routed ICN topology.
• ITS Standard and Core APs may exist together on a routed ICN topology so long
as the maximum number of APs does not exceed 320.
• Only the 1.4 GHz ITS may be installed within a routed ICN topology. The 2.4 GHz
ITS does not support installation within a routed ICN topology.
Refer to Table 1-10 for a list of the device IP address assignments used in a routed
ICN configuration where the ITS infrastructure is installed as a separate subnet to
which up to 22 Database Domains have access via routers.
Note the following regarding Table 1-10:
• “n” represents the network number and starts at 0 for single ICN systems (i.e.,
Database Domains). This variable increments by 8 from there for additional
IntelliVue Clinical Networks. For example, for ICN 2, “n” would equal 8, for ICN 3,
“n” would equal 16, and so on.
• Route statements are generated (in instances with a Router and without) at the
completion of the Config Wizard.
Summary of Contents for IntelliVue Telemetry System Infrastructure
Page 8: ...viii Contents ...
Page 14: ...xiv About This Guide ...
Page 100: ...3 22 Chapter 3 Installing and Configuring the ITS Figure 3 10 APC Filter Configuration Screen ...
Page 162: ...5 12 Chapter 5 Troubleshooting and Testing ...
Page 168: ...A 6 Chapter A Installing Multiple ITSs at a Single Hospital Site ...
Page 180: ...Index 8 Index ...