![background image](http://html1.mh-extra.com/html/omron/nx-ecc201/nx-ecc201_user-manual_742778318.webp)
13 Troubleshooting
13 - 40
NX-series EtherCAT Coupler Unit User’s Manual (W519)
13-4 Resetting Errors
Current errors in a Slave Terminal are retained, unless you reset them, until you cycle the power supply
or restart the Slave Terminal.
To reset errors, you must remove the cause of the current error. If you reset an error without removing
the cause, the same error will occur again.
Precautions for Correct Use
Resetting the errors does not remove the cause of the error.
Always remove the cause of the error, and then reset the error.
You can use the following methods to reset errors in a Slave Terminal.
Note
On the NS-Series PT, you can only reset all errors for the entire Controller.
Refer to the
Sysmac Studio Version 1 Operation Manual
(Cat. No. W504-E1-07 or later) for Sysmac
Studio operating procedures.
For details on the Reset EtherCAT Error (ResetECError) instruction, refer to the
NJ-series Instructions
Reference Manual
(Cat. No. W502).
Method
Operation
Scope of error
reset
Description
Commands from
Sysmac Studio
Resetting Controller
errors
All errors in the Con-
troller
Reset the Controller error from the Trouble-
shooting Dialog Box on the Sysmac Studio.
All errors in the
Slave Terminal
Refer to
11-27 for details on resetting errors in the
EtherCAT Slave Terminal.
Errors for individu-
ally specified NX
Units
Clearing all memory
for the Slave Termi-
nal
All errors in the
Slave Terminal
If the causes for the Controller errors are
removed, all Controller errors in the Slave
Terminals are reset.
Restarting Slave
Terminals
Commands from the
user program
Resetting Controller
errors in the Ether-
CAT Master Func-
tion Module
All errors in the
EtherCAT Master
Function Module
Execute the Reset EtherCAT Error
(ResetECError) instruction in the user pro-
gram of the NJ-series Controller.
Cycling the Unit
power supply to the
Slave Terminal
---
All errors in the
Slave Terminal
If the causes for the Controller errors are
removed, all Controller errors in the Slave
Terminals are reset.
Summary of Contents for NX-ECC201
Page 38: ...Sections in this Manual 36 NX series EtherCAT Coupler Unit User s Manual W519...
Page 46: ...1 EtherCAT Networks 1 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 56: ...2 Features and System Configuration 2 10 NX series EtherCAT Coupler Unit User s Manual W519...
Page 82: ...4 Part Names and Functions 4 14 NX series EtherCAT Coupler Unit User s Manual W519...
Page 100: ...5 Designing the Power Supply System 5 18 NX series EtherCAT Coupler Unit User s Manual W519...
Page 214: ...9 Setting Up Slave Terminals 9 44 NX series EtherCAT Coupler Unit User s Manual W519...
Page 254: ...11 EtherCAT Coupler Unit Functions 11 30 NX series EtherCAT Coupler Unit User s Manual W519...
Page 278: ...12 Communications Performance 12 24 NX series EtherCAT Coupler Unit User s Manual W519...
Page 340: ...14 Maintenance and Inspection 14 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 400: ...Appendices A 60 NX series EtherCAT Coupler Unit User s Manual W519...
Page 401: ...Index 1 NX series EtherCAT Coupler Unit User s Manual W519 I Index...
Page 405: ......