![background image](http://html1.mh-extra.com/html/omron/nx-ecc201/nx-ecc201_user-manual_742778310.webp)
13 Troubleshooting
13 - 32
NX-series EtherCAT Coupler Unit User’s Manual (W519)
Event name
Synchronization Cycle Setting Error
Event code
350D0000 hex
Meaning
When DC Mode was confirmed, the cycle time was set to a value that made operation impossible. (AL-Sta-
tus Code: 0035 hex)
Source
EtherCAT Master Function Mod-
ule
Source details
EtherCAT Cou-
pler Unit
Detection
timing
When moving
from Pre-Oper-
ational state to
Safe-Opera-
tional state.
Error
attributes
Level
Minor fault
Recovery
Reset the
EtherCAT mas-
ter parameters.
Log category
System
Effects
User program
Continues.
Operation
The Slave Terminal stops in Pre-Operational state.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
When DC Mode was confirmed,
the cycle time was set to a value
that made operation impossible.
Correct the synchronization set-
ting and then download the set-
tings to the EtherCAT master
again.
Set the communications for the
Slave Terminal that are set in the
EtherCAT master according to the
ESI.
Attached
information
None
Precautions/
Remarks
None
Event name
NX Unit Communications Timeout
Event code
84C00000 hex
Meaning
An error occurred in I/O data communications with the NX Units.
Source
EtherCAT Master Function Mod-
ule
Source details
EtherCAT Cou-
pler Unit
Detection
timing
Continuously
Error
attributes
Level
Minor fault
Recovery
Reset error in
EtherCAT Cou-
pler Unit.
Log category
System log
Effects
User program
Continues.
Operation
The Slave Terminal moves to Pre-Operational state.
I/O refreshing for all of the NX Units in the EtherCAT
Slave Terminal stops.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
An NX Unit is not mounted prop-
erly.
Mount the NX Units and End
Cover securely and secure them
with End Plates.
Mount the NX Units and End
Cover securely and secure them
with End Plates.
An NX Unit has failed.
If the error occurs again even after
you make the above correction,
replace the NX Unit.
None
Attached
information
Attached information 1: Unit number of the NX Unit where the error was detected
Precautions/
Remarks
None
Summary of Contents for NX-ECC201
Page 38: ...Sections in this Manual 36 NX series EtherCAT Coupler Unit User s Manual W519...
Page 46: ...1 EtherCAT Networks 1 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 56: ...2 Features and System Configuration 2 10 NX series EtherCAT Coupler Unit User s Manual W519...
Page 82: ...4 Part Names and Functions 4 14 NX series EtherCAT Coupler Unit User s Manual W519...
Page 100: ...5 Designing the Power Supply System 5 18 NX series EtherCAT Coupler Unit User s Manual W519...
Page 214: ...9 Setting Up Slave Terminals 9 44 NX series EtherCAT Coupler Unit User s Manual W519...
Page 254: ...11 EtherCAT Coupler Unit Functions 11 30 NX series EtherCAT Coupler Unit User s Manual W519...
Page 278: ...12 Communications Performance 12 24 NX series EtherCAT Coupler Unit User s Manual W519...
Page 340: ...14 Maintenance and Inspection 14 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 400: ...Appendices A 60 NX series EtherCAT Coupler Unit User s Manual W519...
Page 401: ...Index 1 NX series EtherCAT Coupler Unit User s Manual W519 I Index...
Page 405: ......