![background image](http://html1.mh-extra.com/html/omron/nx-ecc201/nx-ecc201_user-manual_742778180.webp)
9 Setting Up Slave Terminals
9 - 10
NX-series EtherCAT Coupler Unit User’s Manual (W519)
NX Units
Creating the Unit Configuration Information with the Edit Slave Terminal Con-
figuration Tab Page
1
Double-click
EtherCAT
under
Configurations and Setup
in the Multiview Explorer.
Or, right-click
EtherCAT
under
Configurations and Setup
and select
Edit
.
The EtherCAT Configuration Edit Tab Page is displayed for the Configurations and Setup Layer.
2
Drag the EtherCAT Coupler Unit from the Toolbox to the Edit Pane and drop it under the master.
The EtherCAT Coupler Unit is added under the master.
Name
Settable
Description
Data
range
Default
Device name
Yes
The name of the NX Unit.
---
N* (Where * is a
serial number
from 1)
Model name
This is the model number of the NX Unit.
---
---
Product name
This is the product name.
---
---
Unit version
This is the Unit version of the NX Unit.
---
---
NX Unit Number
This number represents the logical position of the NX
Unit. Numbers are automatically assigned from the left-
most mounting position.
---
---
NX Unit Mounting
Setting
Yes
This setting enables or disables the mounting of an NX
Unit. Refer to
11-2 NX Unit Mounting Settings
11-5 for details on this setting.
Enabled or
Disabled
Enabled
Serial Number
This is the serial number of the NX Unit. You can get
the serial number to set the serial number of the actual
EtherCAT Coupler Unit.
---
0
Supply Power/Avail-
able Power [W]
The power that is currently drawn by the NX Units and
the maximum available power supply capacity are
given. This item is for an Additional NX Unit Power Sup-
ply Unit.
---
-/10.00
Power consumption
[W]
This is the power consumption of the NX Units from the
NX bus. This setting applies to Units other than an
Additional NX Unit Power Supply Unit.
---
Refer to the
manual for the
specific NX Unit.
Unit width [mm]
This is the width of the NX Unit.
---
Refer to the
manual for the
specific NX Unit.
I/O allocation set-
tings
Yes
These are the I/O allocation settings for the NX Unit.
Click the
Edit I/O Allocation Settings
Button to edit
these settings. You cannot change this setting for Sys-
tem Units.
---
Refer to the
manual for the
specific NX Unit.
Unit operation set-
tings
Yes
These are the Unit operation settings for the NX Unit.
Click the
Edit Unit Operation Settings
Button to edit
these settings. You cannot change this setting for Sys-
tem Units.
---
Refer to the
manual for the
specific NX Unit.
Setting the Unit Configuration Information
Summary of Contents for NX-ECC201
Page 38: ...Sections in this Manual 36 NX series EtherCAT Coupler Unit User s Manual W519...
Page 46: ...1 EtherCAT Networks 1 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 56: ...2 Features and System Configuration 2 10 NX series EtherCAT Coupler Unit User s Manual W519...
Page 82: ...4 Part Names and Functions 4 14 NX series EtherCAT Coupler Unit User s Manual W519...
Page 100: ...5 Designing the Power Supply System 5 18 NX series EtherCAT Coupler Unit User s Manual W519...
Page 214: ...9 Setting Up Slave Terminals 9 44 NX series EtherCAT Coupler Unit User s Manual W519...
Page 254: ...11 EtherCAT Coupler Unit Functions 11 30 NX series EtherCAT Coupler Unit User s Manual W519...
Page 278: ...12 Communications Performance 12 24 NX series EtherCAT Coupler Unit User s Manual W519...
Page 340: ...14 Maintenance and Inspection 14 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 400: ...Appendices A 60 NX series EtherCAT Coupler Unit User s Manual W519...
Page 401: ...Index 1 NX series EtherCAT Coupler Unit User s Manual W519 I Index...
Page 405: ......