10 I/O Refreshing
10 - 10
NX-series EtherCAT Coupler Unit User’s Manual (W519)
Additional Information
Refer to
A-4 Connecting to Masters from Other Manufacturers
on page A-9 for details on the
operation of I/O refreshing with connections that do not use the built-in EtherCAT port on the
NJ-series CPU Unit.
If you use synchronous I/O refreshing in DC Mode to refresh I/O for EtherCAT Slave Terminals, the pro-
cess data communications cycle and NX bus refresh cycle are automatically synchronized with the pri-
mary period of the CPU Unit. However, the Sysmac Studio does not automatically set the primary
period. You must set the primary period manually. With the primary periodic task in Configurations and
Setup - Task Setup, select the task period in the Period/Execution Condition from the list.
Set the primary period so that it is longer than the NX bus refresh cycle that is automatically calculated
by the Sysmac Studio. If a primary period that is shorter than the NX bus refresh cycle is set, the syn-
chronous I/O refreshing will not operate.
A warning is given if you set the primary period to a value that is smaller than the NX bus refresh cycle
that is automatically calculated by the Sysmac Studio. A warning is displayed next to
EtherCAT
under
Configurations and Setup
in the Multiview Explorer. If you place the cursor on the warning mark, the
required primary period is displayed. Set the primary period accordingly.
Primary Period Setting for Synchronous I/O Refreshing
Summary of Contents for NX-ECC201
Page 38: ...Sections in this Manual 36 NX series EtherCAT Coupler Unit User s Manual W519...
Page 46: ...1 EtherCAT Networks 1 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 56: ...2 Features and System Configuration 2 10 NX series EtherCAT Coupler Unit User s Manual W519...
Page 82: ...4 Part Names and Functions 4 14 NX series EtherCAT Coupler Unit User s Manual W519...
Page 100: ...5 Designing the Power Supply System 5 18 NX series EtherCAT Coupler Unit User s Manual W519...
Page 214: ...9 Setting Up Slave Terminals 9 44 NX series EtherCAT Coupler Unit User s Manual W519...
Page 254: ...11 EtherCAT Coupler Unit Functions 11 30 NX series EtherCAT Coupler Unit User s Manual W519...
Page 278: ...12 Communications Performance 12 24 NX series EtherCAT Coupler Unit User s Manual W519...
Page 340: ...14 Maintenance and Inspection 14 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 400: ...Appendices A 60 NX series EtherCAT Coupler Unit User s Manual W519...
Page 401: ...Index 1 NX series EtherCAT Coupler Unit User s Manual W519 I Index...
Page 405: ......