12 Communications Performance
12 - 12
NX-series EtherCAT Coupler Unit User’s Manual (W519)
(d)
Calculating Tmax-OutTrans
There is only one EtherCAT Slave Terminal, so the value is as follows:
Tmax-OutTrans = T#1-OutTrans
The following parameters are required to calculate T#1-OutTrans.
Refer to
Unit Configuration and Data Sizes in the EtherCAT Slave Terminal
for the values of the above parameters.
Therefore, the value of Tmax-OutTrans is as follows:
(e)
Calculating Tmax-InProc
Tnx-InProc for an NX-ID3343 Digital Input Unit and an NX-AD4608 Analog Input Unit is 0
μ
s.
Therefore, the value of Tmax-InProc is as follows:
(f)
Calculating Tmax-OutProc
Tnx-OutProc of an NX-OD3153 Digital Output Unit is 0
μ
s.
Tnx-OutProc of an NX-DA3605 Analog Output Unit is defined as the conversion time times
the number of points. The conversion time is 10
μ
s per point and there are 4 points.
Therefore, the value of Tmax-OutProc is as follows:
Parameter
Value
Remarks
Total byte size of the out-
put data of the NX Unit
12 bytes
This is the total output data size of the NX Unit.
Number of NX Units
18 Units
---
Number of NX Units with
BOOL output data
8 Units
---
Formula: Tmax-OutTrans = T#1-OutTrans
= 11.71
×
(Integer quotient of total byte size of the output data of the NX Unit
÷
32)
+ 0.46
×
(Remainder of total byte size of the output data of the NX Unit
÷
32)
+ (0.19
×
Number of NX Units with BOOL output data + 2.93)
+ 0.38
×
Number of NX Units
+ 0.014
×
Total bytes size of NX Unit output data
+ 30.40
= 11.71
×
(Integer quotient of 12 bytes
÷
32) + 0.46
×
(Remainder of 12 bytes
÷
32)
+ (0.19
×
8 Units + 2.93) + 0.38
×
18 Units + 0.014
×
12 bytes + 30.40
= 11.71
×
0.00 + 0.46
×
12.00 + (0.19
×
8 Units + 2.93)
+ 0.38
×
18 Units + 0.014
×
12 bytes + 30.40
= 47.38
(Unit:
μ
s)
Formula: Tmax-InProc = 0.00
(Unit:
μ
s)
Formula: Tmax-OutProc = Conversion time
×
Number of points = 10
×
4 points = 40.00
(Unit:
μ
s)
Summary of Contents for NX-ECC201
Page 38: ...Sections in this Manual 36 NX series EtherCAT Coupler Unit User s Manual W519...
Page 46: ...1 EtherCAT Networks 1 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 56: ...2 Features and System Configuration 2 10 NX series EtherCAT Coupler Unit User s Manual W519...
Page 82: ...4 Part Names and Functions 4 14 NX series EtherCAT Coupler Unit User s Manual W519...
Page 100: ...5 Designing the Power Supply System 5 18 NX series EtherCAT Coupler Unit User s Manual W519...
Page 214: ...9 Setting Up Slave Terminals 9 44 NX series EtherCAT Coupler Unit User s Manual W519...
Page 254: ...11 EtherCAT Coupler Unit Functions 11 30 NX series EtherCAT Coupler Unit User s Manual W519...
Page 278: ...12 Communications Performance 12 24 NX series EtherCAT Coupler Unit User s Manual W519...
Page 340: ...14 Maintenance and Inspection 14 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 400: ...Appendices A 60 NX series EtherCAT Coupler Unit User s Manual W519...
Page 401: ...Index 1 NX series EtherCAT Coupler Unit User s Manual W519 I Index...
Page 405: ......