13 - 27
13 Troubleshooting
NX-series EtherCAT Coupler Unit User’s Manual (W519)
13-
3 Che
cking
for Errors an
d T
ro
u
b
lesho
o
tin
g
o
n
t
h
e Sysm
ac S
tu-
dio
13
13-
3-2 Event Co
des fo
r Err
ors and T
roubleshooting Procedure
s
Event name
NX Unit Minor Fault
Event code
35020000 hex
Meaning
A minor fault was detected in an NX Unit.
Source
EtherCAT Master Function Mod-
ule
Source details
NX Unit
Detection
timing
Continuously
Error
attributes
Level
Minor fault
Recovery
Depends on the
error that
occurred.
Log category
Depends on the
error that
occurred.
Effects
User program
Continues.
Operation
Depends on the error that occurred.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
A minor fault level error occurred
in a Unit where an error was
detected.
This event is recorded in the event
log in the Communications Cou-
pler Unit.
Check the cause of the minor fault
in the NX Unit.
---
Attached
information
None
Precautions/
Remarks
None
Event name
Mailbox Setting Error
Event code
35040000 hex
Meaning
An incorrect mailbox setting was detected for the Sync Manager. (AL-Status Code: 0016 hex)
Source
EtherCAT Master Function Mod-
ule
Source details
EtherCAT Cou-
pler Unit
Detection
timing
When moving
from Init state to
Pre-Operational
state.
Error
attributes
Level
Minor fault
Recovery
Reset the
EtherCAT mas-
ter parameters.
Log category
System
Effects
User program
Continues.
Operation
The Slave Terminal stops in Init state.
Sys-
tem-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
An incorrect mailbox setting was
detected for the Sync Manager.
Correct the mailbox setting and
then download the settings to the
EtherCAT master again.
Set the communications for the
Slave Terminal that are set in the
EtherCAT master according to the
ESI.
Attached
information
None
Precautions/
Remarks
None
Summary of Contents for NX-ECC201
Page 38: ...Sections in this Manual 36 NX series EtherCAT Coupler Unit User s Manual W519...
Page 46: ...1 EtherCAT Networks 1 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 56: ...2 Features and System Configuration 2 10 NX series EtherCAT Coupler Unit User s Manual W519...
Page 82: ...4 Part Names and Functions 4 14 NX series EtherCAT Coupler Unit User s Manual W519...
Page 100: ...5 Designing the Power Supply System 5 18 NX series EtherCAT Coupler Unit User s Manual W519...
Page 214: ...9 Setting Up Slave Terminals 9 44 NX series EtherCAT Coupler Unit User s Manual W519...
Page 254: ...11 EtherCAT Coupler Unit Functions 11 30 NX series EtherCAT Coupler Unit User s Manual W519...
Page 278: ...12 Communications Performance 12 24 NX series EtherCAT Coupler Unit User s Manual W519...
Page 340: ...14 Maintenance and Inspection 14 8 NX series EtherCAT Coupler Unit User s Manual W519...
Page 400: ...Appendices A 60 NX series EtherCAT Coupler Unit User s Manual W519...
Page 401: ...Index 1 NX series EtherCAT Coupler Unit User s Manual W519 I Index...
Page 405: ......