54
Connecting to the RS-232C Port at the Host
Section 2-6
CS/CJ-series CPU Units:
CS1G/H-CPU
@@
-E (-V1)
CS1G/H-CPU
@@
H
CJ1G-CPU
@@
Connect to the built-in RS-232C port of the CPU Unit, or the RS-232C port of
the Communications Board. Note that the connection to a peripheral port
must be made via an RS-232C Adapter (CS1W-CN118) specially designed
for connecting to a peripheral port.
PLC Setup
When connecting to a CS/CJ-series CPU Unit, set the following communica-
tions conditions for the PLC Setup. Since the settings shown below are the
PLC default settings for the CPU Unit, no change to the PLC Setup is neces-
sary as long as the baud rate is maintained at 9,600 bps.
Note
Set the Host Link baud rate up to 115,200 bps with the memory switch at the
NT20. When the baud rate is set to 19,200 bps, the PLC Setup of the CPU
Unit need to be changed.
Either set the PLC Setup directly from a Programming Device (Programming
Console), or transmit the PLC Setup made at a Programming Device (CX-
Programmer) to the CPU Unit.
For details on PLC Setup, refer to the
SYSMAC CS Series Operation Manual
(W339-E1-
@
) or
SYSMAC CJ Series Operation Manual
(W393-E1-
@
).
When using the built-in RS-232C port of a CS1G/H, CS1G/H-H, or CJ1G
When using the peripheral port of a CS1G/H, CS1G/H-H, or CJ1G
Item
Setting at Host
Baud rate
Set the same speed as set at the NT20 (See note.)
Stop bits
2 stop bits
Parity
Even
Data length
ASCII 7 bits
Unit No. for the Host Link
00
Word address
Writing Value
Settings
CIO 160
8000
Host Link mode, data length 7 bits,
2 stop bits, even parity
CIO 161
0000
Baud rate: 9,600 bps.
0007
Baud rate: 19,200 bps.
0008
Baud rate: 38,400 bps.
0009
Baud rate: 57,600 bps.
000A
Baud rate: 115,200 bps.
CIO 166
0000
Unit #00
Word address
Writing Value
Settings
CIO 144
8000
Host Link mode, data length 7 bits,
2 stop bits, even parity
CIO 145
0000
Baud rate: 9,600 bps.
0007
Baud rate: 19,200 bps.
0008
Baud rate 38,400 bps.
0009
Baud rate 57,600 bps.
000A
Baud rate 115,200 bps.
CIO 150
0000
Unit #00
Summary of Contents for NT20
Page 1: ...Programmable Terminal Cat No V091 E1 01 NT20 USER S MANUAL ...
Page 2: ...NT series Programmable Terminal User s Manual Produced March 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 15: ...xvi ...
Page 21: ...xxii EC Directives 6 ...
Page 37: ...16 Before Operating Section 1 6 ...
Page 153: ...132 Transferring the Resource Data Section 3 11 ...
Page 185: ...164 Numeral Setting Section 4 8 ...
Page 267: ...246 Key to Programs Section 6 8 ...
Page 281: ...260 Specifications Appendix A ...
Page 285: ...264 Transporting and Storing PTs Appendix C ...
Page 303: ...282 Function Restrictions Depending on the Support Tool Appendix I ...
Page 307: ...286 Index ...
Page 309: ...288 Revision History ...