![background image](http://html.mh-extra.com/html/omron/nt20/nt20_user-manual_744538073.webp)
52
Connecting to the RS-232C Port at the Host
Section 2-6
C200HX/HG/HE(-Z)E: Serial Communications Board Port B
CPM1: Peripheral Port Connection through a CPM1-CIF01 RS-232C Adapter
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on
CS1-series PLCs. The CPM2C’s communications port handles both RS-232C
and peripheral port connections, which are divided internally. Therefore, when
using the CPM2C, it is necessary to select RS-232C or peripheral port con-
nections, according to the kind of cable and port (on the cable) used, as
shown in the following table. Refer to the
CPM2C Operation Manual
for more
details.
Setting the DIP Switches of a C200HX/HG/HE(-Z)E, CQM1, or CQM1H
When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H, the DIP switches on
the front panel must be set as shown below in order to make the settings in
the PLC Setup (in the DM Area) effective.
Word
Writing Value
Settings
DM6550
0001
Host Link mode, no CTS control
Communications conditions set by the contents of DM
DM6551
0303
Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
0304
Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
DM6553
0000
Unit # 00
Word
Writing Value
Settings
DM6650
0001
Host Link mode
Communications conditions set by the contents of DM
DM6651
0303
Data length 7 bits, 2 stop bits, even parity, baud rate:
9,600 bps
0304
Data length 7 bits, 2 stop bits, even parity, baud rate:
19,200 bps
DM6653
0000
Unit # 00
Port connecting to PT
PLC Setup
RS-232C port (D-Sub 9-pin) of CPM2C-CN111
Built-in RS-232C port settings
Peripheral port of CPM2C-CN111
Peripheral port settings
RS-232C port (D-Sub 9-pin) of CS1W-CN118
Built-in RS-232C port settings
Peripheral port of CS1W-CN114
Peripheral port settings
Peripheral port
RS-232C port
(D-Sub 9-pin, female)
CPM2C-CN111
CPM2C
RS-232C port
(D-Sub 9-pin, female)
CS1W-CN118
CPM2C
Peripheral port
CS1W-CN114
CPM2C
Summary of Contents for NT20
Page 1: ...Programmable Terminal Cat No V091 E1 01 NT20 USER S MANUAL ...
Page 2: ...NT series Programmable Terminal User s Manual Produced March 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 15: ...xvi ...
Page 21: ...xxii EC Directives 6 ...
Page 37: ...16 Before Operating Section 1 6 ...
Page 153: ...132 Transferring the Resource Data Section 3 11 ...
Page 185: ...164 Numeral Setting Section 4 8 ...
Page 267: ...246 Key to Programs Section 6 8 ...
Page 281: ...260 Specifications Appendix A ...
Page 285: ...264 Transporting and Storing PTs Appendix C ...
Page 303: ...282 Function Restrictions Depending on the Support Tool Appendix I ...
Page 307: ...286 Index ...
Page 309: ...288 Revision History ...