![background image](http://html.mh-extra.com/html/omron/nt20/nt20_user-manual_744538212.webp)
191
Lamps, Touch Switches, Numeral Setting
Section 5-3
5-3
Lamps, Touch Switches, Numeral Setting
5-3-1
Allocation Bits and Display of Lamps
Lamps are controlled by allocating them to the PLC bits. Set the area and bit
number.
• Available Allocation Bits
The lamps can be allocated to the following PLC areas:
❍
: OK
×
: NG
Since the AR area bits of the CVM1/CV series PLCs are allocated to the sys-
tem, they cannot be used for purposes other than the system use.
The range of respective area varies with the type of PLC.
Note
(1) LR 00000 to LR 00199 are converted to CIO 01000 to CIO 01199.
(2) The EM Area is supported only by the C200HX/HG/HE-(Z)E PLCs.
To set the data memory (DM), specify the word number and then the bit num-
ber (00 to 15).
Symbol
C-series
Alloca-
tion
CVM1/CV -series
Alloca-
tion
CS/CJ-series
Alloca-
tion
None
IR Area
❍
CIO Area
❍
CIO Area
❍
H
HR Area
❍
---
---
HR Area
Not for
Host Link
A
AR Area
❍
AR Area
×
AR Area
❍
L
LR Area
❍
---
---
LR Area (See note 1.)
Not for
Host Link
T
TC Area
Timer PVs
×
TC Area
Timer PVs
×
TC Area
Timer PVs
×
TU
---
---
---
---
TC area,
Timer Completion Flags
×
C
TC Area
Counter PVs
×
TC Area
Counter PVs
×
TC Area
Counter PVs
×
CU
---
---
---
---
TC area,
Counter Completion Flags
×
W
---
---
---
---
WR
Not for
Host Link
TK
---
---
---
---
Task Flags
×
D
DM Area
❍
DM Area
❍
DM Area
❍
E
EM Area
(See note 2.)
❍
EM Area
Current bank
Not for
Host Link
EM Area
Current bank
Not for
Host Link
E0_to EC_
---
---
---
---
EM Area
EM bank 0 to C
Not for
Host Link
Summary of Contents for NT20
Page 1: ...Programmable Terminal Cat No V091 E1 01 NT20 USER S MANUAL ...
Page 2: ...NT series Programmable Terminal User s Manual Produced March 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 15: ...xvi ...
Page 21: ...xxii EC Directives 6 ...
Page 37: ...16 Before Operating Section 1 6 ...
Page 153: ...132 Transferring the Resource Data Section 3 11 ...
Page 185: ...164 Numeral Setting Section 4 8 ...
Page 267: ...246 Key to Programs Section 6 8 ...
Page 281: ...260 Specifications Appendix A ...
Page 285: ...264 Transporting and Storing PTs Appendix C ...
Page 303: ...282 Function Restrictions Depending on the Support Tool Appendix I ...
Page 307: ...286 Index ...
Page 309: ...288 Revision History ...