166
Other HFU Functions
Section 5-3
• Temperature Controller Error
The Temperature Controller Error output will turn ON when any bit between
bit 0 and bit 13 is ON in the Device A Status. It can be used to output EJ1
error status. Refer
Status Lists
on page 255 for details on Device A Status.
■
Example
Example 1: Switch all channels between Run and Stop according to the ON/
OFF status of the event input.
Example 2: Switch all channel banks according to the ON/OFF status of the
event input.
Note
When assigning bus I/O, disable all bus I/O assignments first and
then make the settings.
BUS1
BUS2
Outputs the ON/OFF status
of the event input.
Switches between Run/Stop based
on the bus ON/OFF status.
CPU
CPU
CPU
BUS3
EV1
HFU
TC2
TC4
EDU
Model
Parameter name
Set Value
HFU
Bus Output 3 Assignment Event input 1
TC2
Bus Input 3 Assignment
All channels Run (0)/Stop
(1)
TC4
Bus Input 3 Assignment
All channels Run (0)/Stop
(1)
Outputs the ON/OFF status
of the event input.
Switches banks based on
the bus ON/OFF status.
CPU
CPU
BUS1
BUS2
BUS3
EV1
HFU
TC4
EDU
EV2
CPU
TC4
Model
Parameter name
Set Value
HFU
Bus Output 1 Assignment Event input 1
Bus Output 2 Assignment Event input 2
TC4
Bus Input 1 Assignment
Bank for all channels (bit 0)
Bus Input 2 Assignment
Bank for all channels (bit 1)
Bus Output 1 Assignment Disabled
Bus Output 2 Assignment Disabled
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......