239
Parameter List
Appendix
Vari-
able
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
D3
(93)
Can be
changed
during
operation.
0100
02A0
Bank 3 Set Point - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0101
02A1
Bank 3 Proportional Band - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note 2.)
8.0
EU
BANK
●
---
0102
02A2
Bank 3 Integral Time - CH1
H' 00000000 to H' 00000F9F (0 to 3999)
233
s
BANK
●
---
0103
02A3
Bank 3 Derivative Time - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9)
40.0
s
BANK
●
---
0104
02A4
Bank 3 SP Ramp Rise Value - CH1
H' 00000000 to H' 0000270F (0 to 9999) (See note 1.)
(Function stops when set to 0.)
0
EU/s or
EU/min
BANK
●
---
0105
02A5
Bank 3 SP Ramp Fall Value - CH1
H' 00000000 to H' 0000270F (0 to 9999) (See note 1.)
(Function stops when set to 0.)
0
EU/s or
EU/min
BANK
●
---
Not used.
0107
02A7
Bank 3 Manual Reset Value - CH1
H' 00000000 to H' 000003E8 (0.0 to 100.0)
50.0
%
BANK
●
---
0108
02A8
Bank 3 Cooling Coefficient - CH1
H' 00000001 to H' 0000270F (0.01 to 99.99)
1.00
---
BANK
●
---
0109
02A9
Bank 3 Dead Band - CH1
H' FFFFF831 to H' 0000270F (
−
199.9 to 999.9) (See note
2.)
0.0
EU
BANK
●
---
Not used.
010D
02AD
Bank 3 Alarm Value 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
010E
02AE
Bank 3 Alarm Upper Limit Value 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
010F
02AF
Bank 3 Alarm Lower Limit Value 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0110
02B0
Bank 3 Alarm Value 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0111
02B1
Bank 3 Alarm Upper Limit Value 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0112
02B2
Bank 3 Alarm Lower Limit Value 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0113
02B3
Bank 3 Alarm Value 3 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0114
02B4
Bank 3 Alarm Upper Limit Value 3 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0115
02B5
Bank 3 Alarm Lower Limit Value 3 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0116
02B6
Bank 3 Proportional Band
(Cooling) - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note 2.)
8.0
EU
BANK
●
---
0117
02B7
Bank 3 Integral TIme
(Cooling) - CH1
H' 00000000 to H' 00000F9F (0 to 3999)
233
s
BANK
●
---
0118
02B8
Bank 3 Derivative Time
(Cooling) - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9)
40.0
s
BANK
●
---
Not used.
0200
04A0
Bank 3 Set Point - CH2
The rest are the same as channel 1.
···
···
···
0300
06A0
Bank 3 Set Point - CH3
TC4
---
··
·
··
·
··
·
0400
08A0
Bank 3 Set Point - CH4
TC4
---
···
···
···
V1.2
V1.2
V1.2
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......