Minimum Configuration for Control
Section 3-1
4.
The following table shows the related parameter settings for this example.
CX-Thermo Basic Mode Setting Example
Setting example
Remarks
EJ1N-TC2A-QNHB 0
---
---
CH1
Control in progress parameters
Bank 0
Bank 0 Set Point - CH1
150
°
C
Bank 0 Proportional Band - CH1
8.0
°
C
Default
Bank 0 Integral Time - CH1
233 s
Default
Bank 0 Derivative Time - CH1
40.0 s
Default
Bank 0 Alarm Value 1 - CH1
0
°
C
Bank 0 Alarm Upper Limit Value 1 - CH1 0
°
C
Upper limit alarm; not used.
Bank 0 Alarm Lower Limit Value 1 - CH1 0
°
C
Upper limit alarm; not used.
Bank 0 Alarm Value 2 - CH1
0
°
C
Bank 0 Alarm Upper Limit Value 2 - CH1 0
°
C
Upper limit alarm; not used.
Bank 0 Alarm Lower Limit Value 2 - CH1 0
°
C
Upper limit alarm; not used.
Adjustment settings
Manual MV - CH1
0.0%
Disabled in Auto mode
HB/HS/OC settings 1
---
---
Heater Burnout 1 Detection
0.0 A
HB alarm OFF
Heater Burnout 2 Detection
0.0 A
HB alarm OFF
Control stopped parameters
---
---
Input settings
Input Type - CH1
5: Thermocouple (K)
Temperature Unit - CH1
°
C
Output settings
---
---
Control Period 1
2
OUT1 control period: 2 s
Alarm settings
---
---
Alarm 1 Type - CH1
2: Upper-limit alarm
Alarm 2 Type - CH1
2: Upper-limit alarm
Operation commands
---
---
RUN - CH1
STOP - CH1
Manual - CH1
Auto - CH1
100% AT Execute - CH1
AT Cancel - CH1
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......