![background image](http://html1.mh-extra.com/html/omron/ej1-ethercat/ej1-ethercat_user-manual_742375269.webp)
244
Parameter List
Appendix
DA
(9A)
Can be
changed
during
opera-
tion.
(See
note
2.)
0140
F040
G3ZA1 - CH1 Control Variable Monitor
H' 00000000 H' 000003E8 (0.0 to 100.0)
0.0
%
NUM
●
---
0141
F041
G3ZA1 - CH2 Control Variable Monitor
H' 00000000 H' 000003E8 (0.0 to 100.0)
0.0
%
NUM
●
---
0142
F042
G3ZA1 - CH3 Control Variable Monitor
H' 00000000 H' 000003E8 (0.0 to 100.0)
0.0
%
NUM
●
---
0143
F043
G3ZA1 - CH4 Control Variable Monitor
H' 00000000 H' 000003E8 (0.0 to 100.0)
0.0
%
NUM
●
---
0144
F044
G3ZA1 - CH1 Status
---
---
---
NUM
●
---
0145
F045
G3ZA1 - CH2 Status
---
---
---
NUM
●
---
0146
F046
G3ZA1 - CH3 Status
---
---
---
NUM
●
---
0147
F047
G3ZA1 - CH3 Status
---
---
---
NUM
●
---
0148
F048
G3ZA1 - CT1 Effective Current Monitor
H' 00000000 H' 00000672 (0.0 to 165.0)
0.0
A/%
NUM
●
---
0149
F049
G3ZA1 - CT2 Effective Current Monitor
H' 00000000 H' 00000672 (0.0 to 165.0)
0.0
A/%
NUM
●
---
014A
F04A
G3ZA1 - CT3 Effective Current Monitor
H' 00000000 H' 00000672 (0.0 to 165.0)
0.0
A/%
NUM
●
---
014B
F04B
G3ZA1 - CT4 Effective Current Monitor
H' 00000000 H' 00000672 (0.0 to 165.0)
0.0
A/%
NUM
●
---
014C
F04C
G3ZA1 - CT1 Heater ON Current Monitor
H' 00000000 to H' 000000A5 (0 to 165)
0
A/%
NUM
●
---
014D
F04D
G3ZA1 - CT2 Heater ON Current Monitor
H' 00000000 to H' 000000A5 (0 to 165)
0
A/%
NUM
●
---
014E
F04E
G3ZA1 - CT3 Heater ON Current Monitor
H' 00000000 to H' 000000A5 (0 to 165)
0
A/%
NUM
●
---
014F
F04F
G3ZA1 - CT4 Heater ON Current Monitor
H' 00000000 to H' 000000A5 (0 to 165)
0
A/%
NUM
●
---
0150
F050
G3ZA1 - CT1 Heater OFF Current Moni-
tor
H' 00000000 to H' 000000A5 (0 to 165)
0
A/%
NUM
●
---
0151
F051
G3ZA1 - CT2 Heater OFF Current Moni-
tor
H' 00000000 to H' 000000A5 (0 to 165)
0
A/%
NUM
●
---
0152
F052
G3ZA1 - CT3 Heater OFF Current Moni-
tor
H' 00000000 to H' 000000A5 (0 to 165)
0
A/%
NUM
●
---
0153
F053
G3ZA1 - CT4 Heater OFF Current Moni-
tor
H' 00000000 to H' 000000A5 (0 to 165)
0
A/%
NUM
●
---
0154
F054
Version ---
---
---
NUM
●
---
0180
F080
G3ZA1 - Send Standby Time (See note 1.)
H' 00000000 to H' 00000063 (0 to 99)
1
ms
NUM
●
---
0181
F081
G3ZA1 - Communications Timeout Time
(See note 1.)
H' 00000000 to H' 0000003C (0 to 60)
(Function stops when set to 0.)
0
min
NUM
●
---
0182
F082
G3ZA1 - Setting Operation for Errors
H' 00000000: Continue with error clear (0)
H' 00000001: Continue without error clear (1)
H' 00000002: Stop (2)
0
---
NUM
●
---
0183
F083
G3ZA1 - Offset Value
H' 00000000 to H' 000003E8 (0.0 to 100.0)
20.0
%
NUM
●
---
0184
F084
G3ZA1 - Hysteresis
H' 00000001 to H' 0000000A (1 to 10)
1
A
NUM
●
---
0185
F085
G3ZA1 - SSR Drive Selection
H' 00000000: Zero-cross SSR for single-phase
heater, optimum cycle control (0)
H' 00000001: Non-zero-cross SSR for single-
phase heater, soft-start optimum cycle control
(1)
H' 00000002: Zero-cross SSR for three-phase
heater, three-phase optimum cycle control (2)
0
---
NUM
●
---
0186
F086
G3ZA1 - Current Monitor Display Selec-
tion
H' 00000000: 0 to 50 A (0)
H' 00000001: 0 to 150 A (1)
H' 00000002: 0% to 100% (2)
0
---
NUM
●
---
0187
F087
G3ZA1 - Communications Hysteresis
H' 00000000 to H' 0000012C (0.0 to 30.0)
1.0
%
NUM
●
---
0188
F088
G3ZA1 - Communications Timeout Time
2 (See note 1.)
H' 00000000: Disabled
H' 00000001 to H' 00000E10 (1 to 3600)
0
s
NUM
●
---
0189
F089
G3ZA1 - CT1 Assignment (See note 1.)
H' 00000000: Disabled (0)
H' 00000001: ch1 (1)
H' 00000002: ch2 (2)
H' 00000003: ch3 (3)
H' 00000004: ch4 (4)
1
---
NUM
●
---
018A
G3ZA1 - CT2 Assignment (See note 1.)
2
---
NUM
●
---
018B
G3ZA1 - CT3 Assignment (See note 1.)
3
---
NUM
●
---
018C
G3ZA1 - CT4 Assignment (See note 1.)
4
---
NUM
●
---
01C0
F08A
G3ZA1 - CH1 Soft Increase Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
20.0
s
NUM
●
---
01C1
F08B
G3ZA1 - CH2 Soft Increase Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
20.0
s
NUM
●
---
01C2
F08C
G3ZA1 - CH3 Soft Increase Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
20.0
s
NUM
●
---
01C3
F0C0
G3ZA1 - CH4 Soft Increase Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
20.0
s
NUM
●
---
01C4
F0C1
G3ZA1 - CH5 Soft Increase Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
20.0
s
NUM
●
---
01C5
F0C2
G3ZA1 - CH6 Soft Increase Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
20.0
s
NUM
●
---
01C6
F0C3
G3ZA1 - CH7 Soft Increase Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
20.0
s
NUM
●
---
01C7
F0C4
G3ZA1 - CH8 Soft Increase Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
20.0
s
NUM
●
---
01C8
F0C5
G3ZA1 - CH1 Soft Decrease Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
0.0
s
NUM
●
---
01C9
F0C6
G3ZA1 - CH2 Soft Decrease Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
0.0
s
NUM
●
---
01CA
F0C7
G3ZA1 - CH3 Soft Decrease Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
0.0
s
NUM
●
---
01CB
F0C8
G3ZA1 - CH4 Soft Decrease Time
H' 00000000 to H' 000003E7 (0.0 to 99.9)
0.0
s
NUM
●
---
Vari-
able
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HF
U
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
V2
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......