Parameter List
Appendix
Note
The decimal point position is determined by the sensor selection. In this case, however, the 0 (****) dec-
imal point position setting will be treated as a setting of 1 (***.*).
Variable
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
E3 (A3)
Can be
changed
while
stopped.
Not used.
0100
0360
Alarm 1 Type - CH1
H' 00000000: Alarm function OFF (0)
H' 00000001: Upper and lower limit alarm (1)
H' 00000002: Upper limit alarm (2)
H' 00000003: Lower limit alarm (3)
H' 00000004: Upper and lower limit range alarm (4)
H' 00000005: Upper and lower limit alarm with standby
sequence (5)
H' 00000006: Upper limit alarm with standby sequence
(6)
H' 00000007: Lower limit alarm with standby sequence
(7)
H' 00000008: Absolute value upper limit alarm (8)
H' 00000009: Absolute value lower limit alarm (9)
H' 0000000A: Absolute value upper limit alarm with
standby sequence (10)
H' 0000000B: Absolute value lower limit alarm with
standby sequence (11)
H' 0000000C: LBA (Loop Burnout Alarm) (12)
2
---
ch
●
---
0101
0361
Alarm 1 Latch - CH1
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
ch
●
---
0102
0362
Alarm 1 Hysteresis - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note.)
0.2
EU
ch
●
---
0103
0363
Alarm 1 Open in Alarm - CH1
H' 00000000: Close in alarm (0)
H' 00000001: Open in alarm (1)
0
---
ch
●
---
0104
0364
Alarm 1 ON Delay - CH1
H' 00000000 to H' 000003E7 (0 to 999)
0
s
ch
●
---
0105
0365
Alarm 1 OFF Delay - CH1
H' 00000000 to H' 000003E7 (0 to 999)
0
s
ch
●
---
0106
0366
Alarm 1 SP Selection - CH1
H' 00000000: Ramp SP (0)
H' 00000001: Target SP (1)
0
---
ch
●
---
0107
0367
Alarm 2 Type - CH1
The rest are the same as Alarm 1.
··
·
··
·
··
·
010E
036E
Alarm 3 Type - CH1
···
···
···
0115
0375
LBA Detection Time - CH1
H' 00000000 to H' 0000270F (0 to 9999)
0
s
ch
●
---
0116
0376
LBA Level - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note.)
8.0
EU
ch
●
---
0117
0377
LBA Band - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9) (See note.)
3.0
EU
ch
●
---
Not used.
0200
0560
Alarm 1 Type - CH2
The rest are the same as channel 1.
··
·
··
·
··
·
0300
0760
Alarm 1 Type - CH3
TC4
---
···
···
···
0400
0960
Alarm 1 Type - CH4
TC4
---
···
···
···
Variable
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
E4 (A4)
Can be
changed
while
stopped.
0100
0380
CT1 Assignment
H' 00000000: Disabled (0)
H' 00000001: Control output 1 (1)
H' 00000002: Control output 2 (2)
H' 00000003: Control output 3 (3)
H' 00000004: Control output 4 (4)
1
---
IO
TC2
---
0101
0381
Heater Burnout 1 Latch
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
IO
TC2
---
0102
0382
Heater Burnout 1 Hysteresis
H' 00000001 to H' 000003E8 (0.1 to 100.0)
0.1
A
IO
TC2
---
0103
0383
HS Alarm 1 Latch
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
IO
TC2
---
0104
0384
HS Alarm 1 Hysteresis
H' 00000001 to H' 000003E8 (0.1 to 100.0)
0.1
A
IO
TC2
---
0105
0385
Heater Overcurrent 1 Latch
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
IO
TC2
---
0106
0386
Heater Overcurrent 1 Hysteresis
H' 00000001 to H' 000003E8 (0.1 to 100.0)
0.1
A
IO
TC2
---
Not used.
0200
0580
CT2 Assignment
The rest are the same as from CT1 Assignment to
Heater Overcurrent 1 Hysteresis.
2
···
···
···
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......