Parameter List
Appendix
Note
(1) The decimal point position is determined by the sensor selection.
(2) The decimal point position is determined by the sensor selection. In this case, however, the 0 (****)
decimal point position setting will be treated as a setting of 1 (***.*).
Vari-
able
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
D2
(92)
Can be
changed
during
operation.
0100
0280
Bank 2 Set Point - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0101
0281
Bank 2 Proportional Band - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note 2.)
8.0
EU
BANK
●
---
0102
0282
Bank 2 Integral Time - CH1
H' 00000000 to H' 00000F9F (0 to 3999)
233
s
BANK
●
---
0103
0283
Bank 2 Derivative Time - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9)
40.0
s
BANK
●
---
0104
0284
Bank 2 SP Ramp Rise Value - CH1
H' 00000000 to H' 0000270F (0 to 9999) (See note 1.)
(Function stops when set to 0.)
0
EU/s or
EU/min
BANK
●
---
0105
0285
Bank 2 SP Ramp Fall Value - CH1
H' 00000000 to H' 0000270F (0 to 9999) (See note 1.)
(Function stops when set to 0.)
0
EU/s or
EU/min
BANK
●
---
Not used.
0107
0287
Bank 2 Manual Reset Value - CH1
H' 00000000 to H' 000003E8 (0.0 to 100.0)
50.0
%
BANK
●
---
0108
0288
Bank 2 Cooling Coefficient - CH1
H' 00000001 to H' 0000270F (0.01 to 99.99)
1.00
---
BANK
●
---
0109
0289
Bank 2 Dead Band - CH1
H' FFFFF831 to H' 0000270F (
−
199.9 to 999.9) (See note
2.)
0.0
EU
BANK
●
---
Not used.
010D
028D
Bank 2 Alarm Value 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
010E
028E
Bank 2 Alarm Upper Limit Value 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
010F
028F
Bank 2 Alarm Lower Limit Value 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0110
0290
Bank 2 Alarm Value 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0111
0291
Bank 2 Alarm Upper Limit Value 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0112
0292
Bank 2 Alarm Lower Limit Value 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0113
0293
Bank 2 Alarm Value 3 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0114
0294
Bank 2 Alarm Upper Limit Value 3 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0115
0295
Bank 2 Alarm Lower Limit Value 3 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
BANK
●
---
0116
0296
Bank 2 Proportional Band
(Cooling) - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note 2.)
8.0
EU
BANK
●
---
0117
0257
Bank 2 Integral TIme
(Cooling) - CH1
H' 00000000 to H' 00000F9F (0 to 3999)
233
s
BANK
●
---
0118
0258
Bank 2 Derivative Time
(Cooling) - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9)
40.0
s
BANK
●
---
Not used.
0200
0480
Bank 2 Set Point - CH2
The rest are the same as channel 1.
···
···
···
0300
0680
Bank 2 Set Point - CH3
TC4
---
···
···
···
0400
0880
Bank 2 Set Point - CH4
TC4
---
···
···
···
V1.2
V1.2
V1.2
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......