241
Parameter List
Appendix
Note
(1) The decimal point position is determined by the sensor selection.
(2) The decimal point position is determined by the sensor selection. In this case, however, the 0 (****)
decimal point position setting will be treated as a setting of 1 (***.*).
Vari-
able
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
D5
(95)
Can be
changed
during
operation.
0100
02E0
Input Digital Filter - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9)
0.0
s
ch
●
---
0101
02E1
Input Value 1 for Input Correction -
CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
0
EU
ch
●
---
0102
02E2
Input Shift 1 - CH1
H' FFFFF831 to H' 0000270F (
−
199.9 to 999.9) (See note 2.) 0.0
EU
ch
●
---
0103
02E3
Input Value 2 for Input Correction -
CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
1000
EU
ch
●
---
0104
02E4
Input Shift 2 - CH1
H' FFFFF831 to H' 0000270F (
−
199.9 to 999.9) (See note 2.) 0.0
EU
ch
●
---
0105
02E5
MV at PV Error - CH1
Standard Control:
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
0
%
ch
●
---
Heating and Cooling Control:
H' FFFFFBE6 to H' 0000041A (
−
105.0 to 105.0)
0106
02E6
MV at Stop - CH1
Standard Control:
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
0
%
ch
●
---
Heating and Cooling Control:
H' FFFFFBE6 to H' 0000041A (
−
105.0 to 105.0)
Not used.
0109
02E9
MV Upper Limit - CH1
Standard Control:
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
105.0
%
ch
●
---
Heating and Cooling Control:
H' 00000000 to H' 0000041A (
−
0.0 to 105.0)
010A
02EA
MV Lower Limit - CH1
Standard Control:
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
−
105.0
%
ch
●
---
Heating and Cooling Control:
H' FFFFFBE6 to H' 00000000 (
−
105.0 to 0.0)
010B
02EB
Hysteresis (Heating) - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note 2.)
1.0
EU
ch
●
---
010C
02EC
Hysteresis (Cooling) - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note 2.)
1.0
EU
ch
●
---
010D
02ED
Alpha - CH1
H' 00000000 to H' 00000064 (0.00 to 1.00)
0.65
---
ch
●
---
010E
02EE
Manual MV - CH1
Standard Control:
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
0
%
ch
●
---
Heating and Cooling Control:
H' FFFFFBE6 to H' 0000041A (
−
105.0 to 105.0)
010F
02EF
SP Upper Limit - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
9999
EU
ch
●
---
0110
02F0
SP Lower Limit - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.)
−
1999
EU
ch
●
---
0111
02F1
Disturbance Gain - CH1
H' FFFFFF9C to H' 00000064 (
−
1.00 to 1.00)
0.65
---
ch
●
---
0112
02F2
Disturbance Time Constant - CH1
H' 00000001 to H' 0000270F (0.01 to 99.99)
1.00
---
ch
●
---
0113
02F3
Disturbance Rectification Band - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9) (See note 2.)
0.0
EU
ch
●
---
0114
02F4
Disturbance Judgment Width - CH1
H' FFFFF831 to H' 0000270F (
−
199.9 to 999.9) (See note 2.) 0.0
EU
ch
●
---
Not used.
0200
04E0
Input Digital Filter - CH2
The rest are the same as channel 1.
··
·
··
·
··
·
0300
06E0
Input Digital Filter - CH3
TC4
---
···
···
···
0400
08E0
Input Digital Filter - CH4
TC4
---
···
···
···
Vari-
able
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
D6
(96)
Can be
changed
during
operation.
0100
0300
Heater Burnout 1 Detection
H' 00000000 to H' 000003E8 (0.0 to 100.0)
0.0
A
IO
TC2
---
0101
0301
HS Alarm 1
H' 00000000 to H' 000003E8 (0.0 to 100.0)
100.0
A
IO
TC2
---
0102
0302
Heater Overcurrent 1 Detection
H' 00000000 to H' 000003E8 (0.0 to 100.0)
100.0
A
IO
TC2
---
Not used.
0200
0500
Heater Burnout 2 Detection
The rest are the same as from Heater Burnout Detection 1 to Heater Overcurrent Detection 1.
···
···
···
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......