25
Wiring Terminals
Section 2-2
Use a JST Mfg. Co. Ltd. PA connector.
Housings
Model: PAP-02V-S
Crimp Terminals
Model: SPHD-001T-P0.5
Use an EJ1-CBLA050 Cable (manufactured by OMRON).
The EJ1 contains 120
Ω
of terminating resistance. Connect a terminating
resistor (110 to 125
Ω
, 1/2 W) only to the end G3ZA node.
Connect the black line with a white stripe
to terminal 1 on the G3ZA and the black
line with no stripe to terminal 2.
Set the baud rate to 57.6 kbps
(default value) using key
operations. For details, refer to
the
G3PW Operation Manual.
EJ1-CBLA050 (order separately)
(cable length: 5 m)
Connecting to the G3PW Power Controller
1
2
B (
+
)
A (
−
)
TC4/2
CN1