Setting Output Specifications
Section 4-2
Example: Making All TC4 Outputs into CH1 Control Output (Heating) with Dif-
ferent Slopes
4-2-6
Transfer Outputs
Output 1 and output 2 on Controllers with linear outputs can be used as trans-
fer outputs. Use the following procedure.
1,2,3...
1.
Set the parameter to be output on the transfer output.
The parameter to be output is set using the Control Output Assignment pa-
rameter. Select one of the following values. Refer to
4-2-1 Control Output
Assignments
for details on the assigning the control output.
Process Value, Internal SP, Local SP, Remote SP, Transfer Output (Heat-
ing), Transfer Output (Cooling)
2.
Set the type of linear output. Use the following parameter.
3.
Set the output range for the transfer output.
The range set for output scaling is used as the output range for the transfer
output. Refer to
4-2-5 Output Scaling
for information on output scaling.
■
Example:
The following example outputs the process value on a transfer output.
0.0%
100.0%
100.0%
Output 1
80.0%
Actual output
Set value of control
output assignment
40.0%
60.0%
Output 2
Output 3
Output 4
Output
Parameter name
Set value
Output 1
Control output 1 assignment
CH1 Control out-
put (heating)
Output Scaling Upper Limit 1 100
Output Scaling Lower Limit 1 0
0
Output 2
Control output 2 assignment
CH1 Control out-
put (heating)
Output Scaling Upper Limit 2 80
Output Scaling Lower Limit 2 0
Decimal Point C2
0
Output 3
Control output 3 assignment
CH1 Control out-
put (heating)
Output Scaling Upper Limit 3 60
Output Scaling Lower Limit 3 0
Decimal Point C3
0
Output 4
Control output 4 assignment
CH1 Control out-
put (heating)
Output Scaling Upper Limit 4 40
Output Scaling Lower Limit 4 0
Decimal Point C4
0
Variable type
Parameter name
Setting range
Default
E1/A1
Linear Output 1/2 Type
(I/O) 0: 4-20 mA
1: 0-20 mA
0
Conditions for use
A Controller with linear outputs must be used.
Parameter
Default
Input Type
6 (
−
20.0 to 500.0
°
C)
Control Output 1 Assignment
43 (channel 1 process value)
Linear Output 1 Type
1 (0 to 20 mA)
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......