Control Linked to a Host Device
Section 3-3
3-3-3
Setup
TC4
Refer to
3-2 Multi-channel Control
for details on the EJ1
@
-TC4 settings.
HFU
The settings are made through communications. The CX-Thermo Support
Software can be connected using an E58-CIFQ1 Connecting Cable to set the
parameters from a personal computer.
• The following table shows the parameters related to communications
between the EJ1 and PLC, as well as example settings. Set the unit num-
ber of the HFU to 0.
Note
(1) Displayed when the CX-Thermo's
View Mode
is set to
Advanced
Mode.
Parameter
Set value
Remarks
Initial setting level
Port C Communications Baud Rate
115.2 (kbps)
Default
Port C Communications Data Length (See note 1.)
8 (bit)
Default
Port C Communications Parity (See note 1.)
Even
Default
Port C Communications Stop Bits (See note 1.)
1 (bit)
Default
Programless
Common settings
Programless Communications Protocol
NT Link (1: N)
Default
Programless Communications Upload Data Area (See note 1.)
DM
Default
Programless Communications Download Data Area (See note 1.)
DM
Default
Programless Communications Upload Start Address (See note 1.)
0
Default
Programless Communications Download Start Address (See note 1.)
1500
Default
Upload settings
Programless Upload Settings 4
Unit No. 1 - Common - Device A Status
Programless Upload Settings 5
Unit No. 1 - CH1 - Process Value
Programless Upload Settings 6
Unit No. 1 - CH2 - Process Value
Programless Upload Settings 7
Unit No. 1 - CH3 - Process Value
Programless Upload Settings 8
Unit No. 1 - CH4 - Process Value
Programless Upload Settings 9
Unit No. 2 - Common - Device A Status
Programless Upload Settings 10
Unit No. 2 - CH1 - Process Value
Programless Upload Settings 11
Unit No. 2 - CH2 - Process Value
Programless Upload Settings 12
Unit No. 2 - CH3 - Process Value
Programless Upload Settings 13
Unit No. 2 - CH4 - Process Value
Programless Upload Settings 14
Unit No. 3 - Common - Device A Status
Programless Upload Settings 15
Unit No. 3 - CH1 - Process Value
Programless Upload Settings 16
Unit No. 3 - CH2 - Process Value
Programless Upload Settings 17
Unit No. 3 - CH3 - Process Value
Programless Upload Settings 18
Unit No. 3 - CH4 - Process Value
Programless Upload Settings 19
Unit No. 0 - Common - End Code
.
.
.
.
.
.
Download settings
Programless Download Settings 4
Unit No. 1 - CH1 - Set Point
Programless Download Settings 5
Unit No. 1 - CH2 - Set Point
Programless Download Settings 6
Unit No. 1 - CH3 - Set Point
Programless Download Settings 7
Unit No. 1 - CH4 - Set Point
Programless Download Settings 8
Unit No. 2 - CH1 - Set Point
Programless Download Settings 9
Unit No. 2 - CH2 - Set Point
Programless Download Settings 10
Unit No. 2 - CH3 - Set Point
Programless Download Settings 11
Unit No. 2 - CH4 - Set Point
Programless Download Settings 12
Unit No. 3 - CH1 - Set Point
Programless Download Settings 13
Unit No. 3 - CH2 - Set Point
Programless Download Settings 14
Unit No. 3 - CH3 - Set Point
Programless Download Settings 15
Unit No. 3 - CH4 - Set Point
Programless Download Settings 16
Unit No. 0 - Common - End Code
.
.
.
.
.
.
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......