Parameter List
Appendix
Note
The decimal point position is determined by the sensor selection. In this case, however, the 0 (****) dec-
imal point position setting will be treated as a setting of 1 (***.*).
Variable
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
E5 (A5)
Can be
changed
while
stopped.
0000
9280
AT Calculated Gain
H' 00000001 to H' 00000064 (0.1 to 10.0)
0.8
---
Common
●
---
0001
9281
Limit Cycle MV Amplitude
H' 00000032 to H' 000001F4 (5.0 to 50.0)
20.0
%
Common
●
---
0002
9282
Disturbance Overshoot Adjustment Function
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
Common
●
---
Not used.
0100
03A0
Direct/Reverse Operation - CH1
H' 00000000: Reverse operation (0)
H' 00000001: Direct operation (1)
0
---
ch
●
---
0101
03A1
SP Ramp Time Unit - CH1
H' 00000000: Seconds (0)
H' 00000001: Minutes (1)
1
---
ch
●
---
0102
03A2
AT Hysteresis - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9)
(See note.)
0.8
EU
ch
●
---
0103
03A3
Temporary AT Execution Judgement Deviation -
CH1
H' 00000000 to H' 0000270F (0.1 to 999.9)
(See note.)
150.0
EU
ch
●
---
Not used.
0105
03A5
RT - CH1
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
ch
●
---
0106
03A6
PID/OnOff - CH1
H' 00000000: 2-PID control (0)
H' 00000001: ON-OFF control (1)
0
---
ch
●
---
0107
03A7
Output Mode Selection - CH1
H' 00000000: Standard control (0)
H' 00000001: Heating/cooling control(1)
0
---
ch
●
---
0108
03A8
SP Tracking - CH1
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
ch
●
---
Not used.
010C 03AC
ST - CH1
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
ch
●
---
010D 03AD
ST Stable - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9)
(See note.)
15.0
EU
ch
●
---
010E
03AE
Independent heating/cooling PID method - CH1
H' 00000000: Disabled (0)
H' 00000001: Air cooling (1)
H' 00000002: Water cooling (2)
H' 00000003: Linear (3)
0
---
ch
●
---
Not used.
0200
05A0
Direct/Reverse Operation - CH2
The rest are the same as channel 1.
··
·
··
·
··
·
Note: The SP Tracking - CH2 parameter is supported only by the TC4.
0300
07A0
Direct/Reverse Operation - CH3
Note: The SP Tracking - CH3 parameter cannot be used.
TC4
---
···
···
···
0400
09A0
Direct/Reverse Operation - CH4
Note: The SP Tracking - CH4 parameter cannot be used.
TC4
---
···
···
···
V1.2
V1.2
V1.2
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......