148
Programless Communications
Section 5-1
5-1-5
Operation Command Codes for Programless Communications
The following parameters are executed using operation commands.
Command codes for programless communications operation commands differ
from command codes in CompoWay/F communications because the data
length is limited to 16 bits.
Operation command codes for programless communications can be checked
using the Programless Communications Utility for EJ1 in the CX-Thermo Sup-
port Software.
The Programless Communications Utility for EJ1 can be started under
Start -
Program - OMRON - CX-one - CX-Thermo - Programless Communica-
tions Utility for EJ1
.
Example Calculation of Operation Command Codes for Programless
Communications
Any unit number between 0 and 31 or all Units can be selected.
Any channel between 1 and 4 or all channels can be selected.
• Write mode
• Software Reset
• Run
• Stop
• Manual
• Auto
• AT Execute
• AT Cancel
• Bank 0 Change to
Bank 3 Change
• Alarm 1 to Alarm 3
Latch Cancel
• All Alarm Latch
Cancel
• Save RAM Data
• Register Unit Con-
figuration
Unit No.
Channel
Operation command
Operation command code
(hexadecimal)
All units
All channels Run
2809
Stop
2C09
Manual
3009
Auto
3409
40% AT Execute
3809
100% AT Execute
3C09
AT Cancel
4009
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......