![background image](http://html1.mh-extra.com/html/omron/ej1-ethercat/ej1-ethercat_user-manual_742375265.webp)
240
Parameter List
Appendix
Note
(1) The decimal point position is determined by the sensor selection.
(2) The decimal point position is determined by the sensor selection. In this case, however, the 0 (****)
decimal point position setting will be treated as a setting of 1 (***.*).
Vari-
able
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
D4
(94)
Can be
changed
during
operation.
0100
02C0
Present Bank Set Point - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
0101
02C1
Present Bank Proportional Band - CH1
H' 00000001 to H' 0000270F (1 to 9999) (See note 2.)
8.0
EU
BANK
●
---
0102
02C2
Present Bank Integral Time - CH1
H' 00000000 to H' 00000F9F (0 to 3999)
233
s
BANK
●
---
0103
02C3
Present Bank Derivative Time - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9)
40.0
s
BANK
●
---
0104
02C4
Present Bank SP Ramp Rise Value - CH1
H' 00000000 to H' 0000270F (0 to 9999) (See note 1.)
(Function stops when set to 0.)
0
EU/s or
EU/min
BANK
●
---
BANK
---
0105
02C5
Present Bank SP Ramp Fall Value - CH1
H' 00000000 to H' 0000270F (0 to 9999) (See note 1.)
(Function stops when set to 0.)
0
EU/s or
EU/min
BANK
●
---
Not used.
0107
02C7
Present Bank Manual Reset Value - CH1
H' 00000000 to H' 000003E8 (0.0 to 100.0)
50.0
%
BANK
●
---
0108
02C8
Present Bank Cooling Coefficient - CH1
H' 00000001 to H' 0000270F (0.01 to 99.99)
1.00
---
BANK
●
---
0109
02C9
Present Bank Dead Band - CH1
H' FFFFF831 to H' 0000270F (
−
199.9 to 999.9) (See note
2.)
0.0
EU
BANK
●
---
Not used.
010D 02CD
Present Bank Alarm Value 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
010E
02CE
Present Bank Alarm Upper Limit Value 1 -
CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
010F
02CF
Present Bank Alarm Lower Limit Value 1 -
CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
0110
02D0
Present Bank Alarm Value 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
0111
02D1
Present Bank Alarm Upper Limit Value 2 -
CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
0112
02D2
Present Bank Alarm Lower Limit Value 2 -
CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
0113
02D3
Present Bank Alarm Value 3 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
0114
02D4
Present Bank Alarm Upper Limit Value 3 -
CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
0115
02D5
Present Bank Alarm Lower Limit Value 3 -
CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 1.) 0
EU
BANK
●
---
0116
02D6
Present Bank Proportional Band
(Cooling) - CH1
H' 00000001 to H' 0000270F (0.1 to 999.9) (See note 2.)
8.0
EU
BANK
●
---
0117
02D7
Present Bank Integral TIme
(Cooling) - CH1
H' 00000000 to H' 00000F9F (0 to 3999)
233
s
BANK
●
---
0118
02D8
Present Bank Derivative Time
(Cooling) - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9)
40.0
s
BANK
●
---
Not used.
0200
04C0
Present Bank Set Point - CH2
The rest are the same as channel 1.
···
···
···
0300
06C0
Present Bank Set Point - CH3
TC4
---
···
···
···
0400
08C0
Present Bank Set Point - CH4
TC4
---
···
···
···
V1.2
V1.2
V1.2
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...