130
Programless Communications
Section 5-1
• The following parameters can be set. Up to 300 settings can be made for
version V1.0, up to 600 settings can be made for version
, and up to
1,200 settings can be made for version
.
TC2/4
Note
HFU parameters other than those listed in the following table cannot be used
when making programless upload/download settings. If parameters that do
not appear in the table are used, internal communication errors will occur, and
programless communications will be delayed.
HFU
• Parameters can be set to
Not used
to reserve words for future use.
Note
The words set to
Not used
cannot be used for any other purpose
except the programless function.
• Only channels 1 and 2 can be set for TC2 Units.
• Unit numbers can be between 0 and 31, but one HFU can manage only
up to 16 Basic Units.
CX-Thermo Programless Upload Settings: Setting Screen
Programless upload
settings
Variable types: C4/84, C5/85, D4/94, D5/95, D6/96, and
C9/89 (however, G3ZA1 to G3ZA4)
Programless download
settings
Variable types: D4/94, D5/95, and D6/96
V1.1
V1.2
V1.2
Programless upload
settings
Error status: Refer to the
Error Status
section on page
131.
Programless download
settings
Bit-specified operation commands. Refer to page 152
for details.
V1.2
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......