233
Parameter List
Appendix
Parameter List
If variables without parentheses are used in communications, the set values will be eight-digit (double-word)
data. If variables with parentheses are used in communications, the set values will be four-digit (word) data.
Example:
Variable type C4: Double word (8 digits)
Variable type 84: Word (4 digits)
Variable
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
C0 (80)
Monitor
0000
---
Process Value - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
0001
---
Status - CH1
See
Status Lists
on page 255.
---
---
ch
●
---
0002
---
Internal SP - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
Not used.
0004
---
MV Monitor (Heating) - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
---
%
ch
●
---
0005
---
MV Monitor (Cooling) - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
---
%
ch
●
---
Not used.
0100
---
Process Value - CH2
The rest are the same as channel 1.
···
···
···
0200
---
Process Value - CH3
···
···
···
0300
---
Process Value - CH4
···
···
···
8000
0080
Process Value - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
8001
0081
Process Value - CH2
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
8002
0082
Process Value - CH3
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
8003
0083
Process Value - CH4
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
8004
0084
Channel Alarm Status - CH1
See
Status Lists
on page 255.
---
---
ch
●
---
8005
0085
Channel Alarm Status - CH2
See
Status Lists
on page 255.
---
---
ch
●
---
8006
0086
Channel Alarm Status - CH3
See
Status Lists
on page 255.
---
---
ch
●
---
8007
0087
Channel Alarm Status - CH4
See
Status Lists
on page 255.
---
---
ch
●
---
8008
0088
Channel Status - CH1
See
Status Lists
on page 255.
---
---
ch
●
---
8009
0089
Channel Status - CH2
See
Status Lists
on page 255.
---
---
ch
●
---
800A
008A
Channel Status - CH3
See
Status Lists
on page 255.
---
---
ch
●
---
800B
008B
Channel Status - CH4
See
Status Lists
on page 255.
---
---
ch
●
---
800C
008C
Internal SP - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
800D
008D
Internal SP - CH2
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
800E
008E
Internal SP - CH3
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
800F
008F
Internal SP - CH4
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.)
---
EU
ch
●
---
8010
0090
MV Monitor (Heating) - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
---
%
ch
●
---
8011
0091
MV Monitor (Heating) - CH2
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
---
%
ch
●
---
8012
0092
MV Monitor (Heating) - CH3
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
---
%
ch
●
---
8013
0093
MV Monitor (Heating) - CH4
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
---
%
ch
●
---
8014
0094
Heater Current Value 1 Monitor
H' 00000000 to H' 0000044C (0.0 to 110.0)
---
A
IO
TC2
---
8015
0095
Leakage Current Value 1 Moni-
tor
H' 00000000 to H' 0000044C (0.0 to 110.0)
---
A
IO
TC2
---
8016
0096
Heater Current Value 2 Monitor
H' 00000000 to H' 0000044C (0.0 to 110.0)
---
A
IO
TC2
---
8017
0097
Leakage Current Value 2 Moni-
tor
H' 00000000 to H' 0000044C (0.0 to 110.0)
---
A
IO
TC2
---
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......