111
Other Functions (TC4 and TC2)
Section 4-7
!Caution
If the MV is stored or calculated at the G3ZA and the G3ZA is turned ON
before the EJ1, the controlled variable produced at the G3ZA will be output
(the output may not be 0.0%) until the EJ1 starts operating. When using MV
storage or MV calculation, verify that the controlled variable produced by the
G3ZA is appropriate.
■
Example
In this example, the TC4's channel 1 Control output (heating) is output to
G3ZA channels 1 to 4.
4-7-5
Using the G3PW
Initial Settings
The G3PW cannot be used in the condition in which it is shipped. Make the
following settings.
1,2,3...
1.
Connect the G3PW to a Basic Unit.
Up to eight Units can be connected to one Basic Unit. If more than eight
Units are connected, a configuration error will occur. G3PW Units and
G3ZA Units cannot be used in combination.
2.
Turn ON pin 7 of SW2 on the Basic Unit, and make the following settings:
Set the main setting auto/manual switch on the G3PW to auto (0), set the
event input allocation to no allocation (0) or control method switch (1), set
the main setting auto input switch to communications (1), set the main set-
ting auto/manual switch default mode to auto (0), set the baud rate to
57.6 kbps (3), set the communications unit No. between 1 and 8, and set
the communications main setting acquisition number from 0 to 8. For infor-
mation on the communications main setting acquisition number, refer to
MV Output from the G3PW
on page 114.
Settings can be made for the G3PW using key operations. For details refer
to the
G3PW Power Controller User's Manual
(Cat. No. Z280).
3.
Turn ON the power supply to the Basic Unit and execute a Register Unit
Configuration: Reset operation command. No G3ZA Units are registered
in the default Basic Unit settings.
4.
Turn OFF the power supply to the Basic Unit and then turn ON the power
supply in the following order: G3PW Units and then the Basic Unit. When
the Basic Unit starts, it will automatically scan for connected G3PW Units.
Channel 1 MV
Channel 2 MV
Channel 3 MV
Channel 4 MV
TC4
G3ZA
Operation
Operation
Operation
Operation
Channel 1 controlled variable
Channel 2 controlled variable
Channel 3 controlled variable
Channel 4 controlled variable
Set with the Source
Channel parameter.
Set with the Slope and
Offset parameters.
CH1 Control Output (Heating)
CH2 Control Output (Heating)
CH3 Control Output (Heating)
CH4 Control Output (Heating)
G3ZA settings
Set value
CH1 Source Channel 1
CH2 Source Channel 1
CH3 Source Channel 1
CH4 Source Channel 1
V1.1
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......