Appendix
Device A Status
Note
The above information also applies to the G3PW.
Bit position
Status
Bit description
Meaning
0
1
Bit 0
Device Error
No error
Error
There is a memory error.
Refer to
Device Error Status
.
Bit 1
Configuration Error
No error
Error
There is an error in the device configuration.
Refer to
Configuration Error A Status
, and
Configu-
ration Error B Status
.
Bit 2
Channel Error
No error
Error
There is an error in one of the channels.
Refer to
Error Channel A Status
.
Bit 3
Not used.
Bit 4
Expand Communica-
tions Error
No error
Error
There is an error in communications with the con-
nected G3ZA.
Refer to
Internal Communications Error Status
.
Bit 5
Not used.
Bit 6
Not used.
Bit 7
Not used.
Bit 8
Not used.
Bit 9
Not used.
Bit 10
I/O Error
No error
Error
There is an I/O error.
Refer to
I/O Error Status
.
Bit 11
Lower-level I/O Error
No error
Error
There is an error in the connected G3ZA.
Refer to
Basic Unit/Expand Unit Error Status
.
Bit 12
I/O Alarm
No error
Error
There is an I/O alarm.
Refer to
I/O Alarm A Status
and
I/O Alarm B Status
.
Bit 13
Lower-level I/O Alarm
No error
Error
An alarm has occurred in the connected G3ZA.
Refer to
Basic Unit/Expand Unit Alarm Status
.
Bit 14
I/O Notification
No error
Error
There is an I/O notification.
Refer to
I/O Notification A Status
.
Bit 15
Not used.
C4/84 0000
V1.1
Summary of Contents for EJ1 EtherCAT
Page 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Page 3: ...iv ...
Page 19: ...xx ...
Page 213: ...188 Detailed Description of Services Section 6 4 ...
Page 227: ...202 Detailed Description of Services Section 7 5 ...
Page 303: ...278 Index ...
Page 305: ......