85
Setting Control Specifications
Section 4-3
• Each set value determines the operation for different errors, as shown in
the following table.
Note
Applies to the channel associated with the CT (current transformer).
For example, when the Control Output 1 Assignment is set to Channel 1 Con-
trol Output (Heating) and the CT1 Assignment is set to OUT1, channel 1 will
operate according to the Operation During Error (Selection B) setting if a
heater burnout is detected at CT1.
Since CT1 is associated with channel 1, channel 1 will operate according to
the Operation During Error (Selection B) setting if an error is detected at CT1.
Parameter name
Errors
Operation During Error (Selection B)
(See note.)
• CT Heater Overcurrent
• Heater Burnout (HB) Alarm
• Heater Short (HS) Alarm
• Heater Overcurrent (OC) Alarm
OUT1
Channel 1 Control
Output (Heating)
CT1
Associated by the Control
Output 1 Assignment.
Associated by the
CT1 Assignment.