3 Communications Data for CompoWay/F
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
3-1 V
ariab
le A
rea (Setting
Ran
g
e) List
3
Note: The alarm function can also be used in Digital Controllers without auxiliary output terminals. In this case,
confirm alarm occurrences via the status data.
*1
Valid only with external communications.
*2
Do not set the same set value for more than one event input assignment.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C3 (83)
0016
Event Input
Assignment 1
*2
H'00000000 (0):
None
H'00000001 (1):
RUN (OFF)/RESET (ON)
H'00000002 (2):
RUN (ON)/RESET (OFF)
H'00000003 (3):
Auto/manual switch
H'00000004 (4):
RESET
H'00000005 (5):
RUN
H'00000006 (6):
Hold/clear hold
H'00000007 (7):
Hold
H'00000008 (8):
Advance
H'00000009 (9):
Program No. switch 0
H'0000000A (10): Program No. switch 1
H'0000000B (11): Program No. switch 2
H'0000000C (12): Direct/reverse operation
H'0000000D (13): Program SP mode/fixed SP mode
H'0000000E (14): 100% AT execute/cancel
H'0000000F (15): 40% AT execute/cancel
H'00000010 (16): All PID 100% AT execute/cancel
H'00000011 (17): All PID 40% AT execute/cancel
H'00000012 (18): Setting Change Enable/Disable
H'00000013 (19): Communications Writing
Enable/Disable
*1
H'00000014 (20): Alarm latch cancel
H'00000015 (21): Wait enable (ON)/Disable (OFF)
Initial
setting
C3 (83)
0017
Event Input
Assignment 2
*2
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
C3 (83)
0018
Event Input
Assignment 3
*2
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
C3 (83)
0019
Event Input
Assignment 4
*2
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
C3 (83)
001D
Standby Sequence
Reset
H'00000000 (0): Condition A
H'00000001 (1): Condition B
Advanced
function
setting
C3 (83)
001E
Auxiliary Output 1
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
C3 (83)
001F
Alarm 1 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial
setting
C3 (83)
0020
Auxiliary Output 2
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function
setting
C3 (83)
0021
Alarm 2 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial
setting
C3 (83)
0022
Auxiliary Output 3
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function
setting
C3 (83)
0023
Alarm 3 Hysteresis H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial
setting