5 Communications Data for Modbus
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
5
-1 V
ariab
le A
re
a (Setting
Rang
e) List
5
0502
2501
Initial
Setting/Communications
Protect
H'00000000 (0):
Move to initial setting/communications setting
level is allowed. (Move to advanced function
setting level is displayed.)
H'00000001 (1):
Move to initial setting/communications setting
level is allowed. (Move to advanced function
setting level is not displayed.)
H'00000002 (2):
Move to initial setting/communications setting
level is prohibited.
Protect
0504
2502
Setting Change Protect
H'00000000 (0): OFF (Changing of setup on controller display is
allowed.)
H'00000001 (1): ON (Changing of setup on controller display is
prohibited.)
0506
2503
PF Key Protect
H'00000000 (0): OFF
H'00000001 (1): ON
0508
2504
Move to Protect Level
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
050A
2505
Password to Move to
Protect Level
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
(Can only be set. The monitor value is always H’00000000.)
050C
2506
Parameter Mask Enable
H'00000000 (0): OFF
H'00000001 (1): ON
0600
2600
Manual MV
Standard Models
Standard control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
Position-proportional Models
Close position-proportional control with the Direct Setting of
Position Proportional MV parameter set to ON:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Manual
control
0608
2604
Heater Current 1 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
060A
2605
MV Monitor (Heating)
Standard control:
H'FFFFFFCE to H'0000041A
(
−
5.0 to 105.0)
Heating and cooling control: H'00000000 to H'0000041A
(0.0 to 105.0)
060C
2606
MV Monitor (Cooling)
H'00000000 to H'0000041A (0.0 to 105.0)
060E
2607
Valve Opening Monitor
H'FFFFFF9C to H'0000044C (
−
10.0 to 110.0)
0610
2608
Program No.
H'00000000 to H'00000007 (0 to 7)
0612
2609
Segment No. Monitor
H'00000000 to H'0000001F (0 to 31)
0614
260A
Remaining Standby Time
Monitor
H'00000000 to H'00009959 (hours, minutes)
H'00000000 to H'00009923 (days, hours)
0616
260B
Elapsed Program Time
Monitor
H'00000000 to H'00009959
0618
260C
Remaining Program Time
Monitor
H'00000000 to H'00009959
None
061A
260D
Elapsed Segment Time
Monitor
H'00000000 to H'00009959
061C
260E
Remaining Segment Time
Monitor
H'00000000 to H'00009959
061E
260F
Program Execution
Repetitions Monitor
H'00000000 to H'0000270F (0 to 9999)
Operation
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode