3 Communications Data for CompoWay/F
3 - 24
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
C5 (85)
0004
PID 1 MV Lower Limit
Standard control or position proportional
(closed): H'FFFFFFCE to MV upper limit
−
0.1
(
−
5.0 to MV upper limit
−
0.1)
Heating/cooling control: H'FFFFFBE6 to
H'00000000 (
−
105.0 to 0.0)
PID Setting
C5 (85)
0005
PID 1 Automatic
Selection Range
Upper Limit
Temperature input: H'FFFFF831 to
H'0000270F (
−
1999 to 9999)
Analog input: H'FFFFFFCE to H'0000041A
(
−
5.0 to 105.0)
C5 (85)
0007
PID 1 LBA Detection
Time
H'00000000 to H'0000270F (0 to 9999)
C5 (85)
0008
PID 1 Proportional
Band (Cooling)
H'00000001 to H'0000270F (0.1 to 999.9)
C5 (85)
0009
PID 1 Integral Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is
0.1 s.)
C5 (85)
000A
PID 1 Derivative Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is
0.1 s.)
C5 (85)
000B
PID 1 Dead Band
Temperature input: H'FFFFF831 to
H'0000270F (
−
1999 to 999.9)
Analog input: H'FFFFF831 to H'0000270F
(
−
19.99 to 99.99)
C5 (85)
000C
PID 1 Manual Reset
Value
H'00000000 to H'000003E8 (0.0 to 100.0)
C5 (85)
0010
PID 2 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to
to
C5 (85)
001C
PID 2 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
C5 (85)
0020
PID 3 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to
to
C5 (85)
002C
PID 3 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
C5 (85)
0030
PID 4 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to
to
C5 (85)
003C
PID 4 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
C5 (85)
0040
PID 5 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to
to
C5 (85)
004C
PID 5 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
C5 (85)
0050
PID 6 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
to
to
C5 (85)
005C
PID 6 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
Variable
type
Address
Parameter name
Setting (monitor) value
Level