![Omron E5CC-T Communications Manual Download Page 68](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604068.webp)
3 Communications Data for CompoWay/F
3 - 22
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
*1
The set values for the program specified in the Program Selection parameter are accessed for the following
parameters: No. of Segments Used, Segment Selection, PID Set No., Alarm Values 1 to 4, Alarm Upper
Limits 1 to 4, Alarm Lower Limits 1 to 4, Program Repetitions, Program Link Destination No., Time Signal 1
and 2 Set Segments, Time Signal 1 and 2 ON Times, and Time Signal 1 and 2 OFF Times. Check the set
value of the Program Selection parameter before accessing these parameters.
*2
The set values for the program specified in the Program Selection parameter and the section specified in the
Segment Selection parameter are accessed for the following parameters: Segment Type, Segment SP,
Segment Slope, and Segment Time.
Check the set value of the Program Selection and Segment Selection parameters before accessing these
parameters.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C4 (84)
0000
Program Selection
H'00000000 to H'00000007 (0 to 7)
Program
setting
C4 (84)
0001
Number of
Segments Used
*1
H'00000001 to H'00000020 (32)
C4 (84)
0002
Segment
Selection
*1
H'00000000 to H'0000001F (31)
C4 (84)
0003
Segment Format
*2
H'00000000 (0): Ramp
H'00000001 (1): Soak
H'00000002 (2): Step
C4 (84)
0004
Segment SP
*2
SP Lower Limit to SP Upper Limit
C4 (84)
0005
Segment Slope
*2
H'00000000 to H'0000270F (0 to 9999)
C4 (84)
0006
Segment Time
*2
H'00000000 to H'00009959 (0.00 to 99.59) (hours,
minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes,
seconds)
C4 (84)
0007
PID Set No.
*1
H'00000000 to H'00000008 (0 to 8), (0): Automatic
selection
C4 (84)
0008
Alarm Value 1
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
0009
Alarm Value Upper
Limit 1
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
000A
Alarm Value Lower
Limit 1
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
000B
Alarm Value 2
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
000C
Alarm Value Upper
Limit 2
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
000D
Alarm Value Lower
Limit 2
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
000E
Alarm Value 3
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
000F
Alarm Value Upper
Limit 3
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
0010
Alarm Value Lower
Limit 3
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
0011
Alarm Value 4
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
0012
Alarm Value Upper
Limit 4
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C4 (84)
0013
Alarm Value Lower
Limit 4
*1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
Summary of Contents for E5CC-T
Page 2: ......
Page 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Page 185: ......