3 Communications Data for CompoWay/F
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
3-1 V
ariab
le A
rea (Setting
Ran
g
e) List
3
Note: The alarm function can also be used in Digital Controllers without auxiliary output terminals. In this case,
confirm alarm occurrences via the status data.
*1
The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently
selected PID set is fixed at PID1.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C1 (81)
0016
Integral Time
*1
Standard, heating/cooling, or close
position-proportional control:
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
Floating position-proportional control:
H'00000001 to H'0000270F
(1 to 9999: Integral/derivative time unit is 1 s.)
(0.1 to 999.9: Integral/derivative time unit is 0.1 s.)
Adjustment
C1 (81)
0017
Derivative Time
*1
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81)
0019
Dead Band
H'FFFFF831 to H'0000270F
(
−
199.9 to 999.9 for temperature input)
(
−
19.99 to 99.99 for analog input)
C1 (81)
001A
Manual Reset
Value
H'00000000 to H'000003E8 (0.0 to 100.0)
C1 (81)
001B
Hysteresis
(Heating)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
C1 (81)
001C
Hysteresis
(Cooling)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
C1 (81)
001D
Heater Burnout
Detection 2
H'00000000 to H'000001F4 (0.0 to 50.0)
C1 (81)
001E
HS Alarm 1
H'00000000 to H'000001F4 (0.0 to 50.0)
C1 (81)
001F
HS Alarm 2
H'00000000 to H'000001F4 (0.0 to 50.0)
C1 (81)
0021
Wait Band
H'00000000 (0): OFF
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
C1 (81)
0022
MV at Reset
Standard Models
Standard control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
Position-proportional Models
Close position-proportional control with the Direct
Setting of Position Proportional MV parameter set to
ON:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Floating position-proportional control or the Direct
Setting of Position Proportional MV parameter set to
OFF:
H'FFFFFFFF to H'00000001 (
−
1 to 1)
C1 (81)
0023
MV at PV Error