6 Programless Communications
6 - 48
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
(3) To make the value easier to check, we will change the values that are displayed to
decimal values.
Click the
Display Format
Button in the above dialog box, select the
Word Multi-point
Option in the Monitor Format Area, select the
10 Points
Option in the Word Device Word
Multi-point Format Area, and then click the
OK
Button.
(4) We will check the E5CC-T monitor values.
The area where monitor values are checked is called the upload area.
D0 to D24 is the upload area for the No. 0 Controller (E5CC-T), D70 to D94 is the upload
area for the No. 1 Controller, and D140 to D164 is the upload area for the No. 2 Controller.