3 Communications Data for CompoWay/F
3 - 2
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
3-1
Variable Area (Setting Range) List
•
For communications using a variable type not enclosed in parentheses in the following table, the set
value is double-word data (8 digits). For communications using a variable type enclosed in
parentheses, the set value is single-word data (4 digits).
•
For example, variable type C0 is double-word data (8 digits), and variable type 80 is single-word data
(4 digits).
•
Items expressed in hexadecimal in the "Setting (monitor) value" column are the setting range for
CompoWay/F communications. The values in parentheses are the actual setting range. When there
is a section reference for a setting item, refer to that reference for details.
*1
Not displayed on the Controller display.
*2
When the variable type is 80 (word access), the rightmost 16 bits are read.
*3
When the variable type is 80 (word access), the leftmost 16 bits are read.
*4
If the RUN/RESET parameter is set to RUN, the current program number will be read.
If the RUN/RESET parameter is set to RESET, the program number that is set in the Program No. parameter
will be read.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C0 (80)
0000
PV
Temperature: Use the specified range for each sensor.
Analog:
Scaling lower limit
−
5% FS to Scaling
upper limit +5% FS
Operation
C0 (80)
0001
Status
*1*2
for details.
C0 (80)
0002
Present SP
*1
SP lower limit to SP upper limit
C0 (80)
0003
Heater Current 1
Value Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
C0 (80)
0004
MV Monitor
(Heating)
Standard:
H'FFFFFFCE to H'0000041A
(
−
5.0 to 105.0)
Heating and cooling: H'00000000 to H'0000041A
(0.0 to 105.0)
C0 (80)
0005
MV Monitor
(Cooling)
H'00000000 to H'0000041A (0.0 to 105.0)
C0 (80)
0006
Heater Current 2
Value Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
C0 (80)
0007
Leakage Current 1
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
C0 (80)
0008
Leakage Current 2
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
C0 (80)
000A
Valve Opening
Monitor
H'FFFFFF9C to H'0000044C (
−
10.0 to 110.0)
C0 (80)
000D
PID Set No. Monitor H'00000001 to H'00000008 (1 to 8)
None
C0 (80)
000E
Decimal Point
Monitor
*1
H'00000000 to H'00000003 (0 to 3)
Operation
C0 (80)
0011
Status 2
*1*2
.
C0 (80)
0012
Status
*1*3
.
C0 (80)
0013
Status 2
*1*3
.
C0 (80)
0014
Program No.
Monitor
*4
H'00000000 to H'00000007 (0 to 7)
C0 (80)
0015
Segment No.
Monitor
H'00000000 to H'0000001F (0 to 31)