5 Communications Data for Modbus
5 - 2
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
5-1
Variable Area (Setting Range) List
•
Four-byte Mode
One element uses 4 bytes of data (H'00000000 to H'FFFFFFFF), so specify two-element units.
Reading and writing in 4-byte units is executed by specifying an even address and specifying the
number of elements in multiples of 2.
•
Two-byte Mode
One element uses 2 bytes of data (H'0000 to H'FFFF), so specify one-element units. Reading and
writing in 2-byte data units is executed by specifying 1-element units.
The following table lists the variable area. Items expressed in hexadecimal in the "Setting (monitor)
value" column are the setting range in the Modbus specifications. Values in parentheses "()" are the
actual setting range.
When there is a section reference for a setting item, refer to that reference for details.
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
0000
2000
PV
Temperature: Use the specified range for each sensor.
Analog: Scaling lower limit
−
5% FS to Scaling upper limit + 5% FS
Operation
0002
2001
Status
*1*2
Refer to
for details.
0004
2002
Present SP
*1
SP lower limit to SP upper limit
0006
2003
Heater Current 1 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
0008
2004
MV Monitor (Heating)
Standard:
H'FFFFFFCE to H'0000041A (
−
5.0 to
105.0)
Heating and cooling:
H'00000000 to H'0000041A (0.0 to 105.0)
000A
2005
MV Monitor (Cooling)
H'00000000 to H'0000041A (0.0 to 105.0)
0404
2402
PV
Temperature: Use the specified range for each sensor.
Analog: Scaling lower limit
−
5% FS to Scaling upper limit + 5% FS
0406
2403
Present SP
*1
SP lower limit to SP upper limit
0408
2404
Program No. Monitor
H'00000000 to H'00000007 (0 to 7)
040A
2405
PID Set No. Monitor
H'00000001 to H'00000008 (1 to 8)
None
040C
2406
Status
*1*2
Refer to
for details.
Operation
040E
2407
Status
*1*3
Refer to
for details.
0410
2408
Status 2
*1*2
Refer to
for details.
0412
2409
Status 2
*1*3
Refer to
for details.
0420
2410
Decimal Point Monitor
H'00000000 to H'00000003 (0 to 3)
0500
2500
Operation/Adjustment
Protect
H'00000000 (0) to H'00000005 (5)
0: No control
1: Operation level (PV displayed, PV/SP allowed, others allowed),
program level allowed, adjustment level allowed, PID setting level
prohibited
2: Operation level (PV displayed, PV/SP allowed, others allowed),
program level allowed, adjustment level prohibited, PID setting
level prohibited
3: Operation level (PV displayed, PV/SP allowed, others allowed),
program level prohibited, adjustment level prohibited, PID setting
level prohibited
4: Operation level (PV displayed, PV/SP allowed, others prohibited),
program level prohibited, adjustment level prohibited, PID setting
level prohibited
5: Operation level (PV displayed, PV/SP displayed, others
prohibited), program level prohibited, adjustment level prohibited,
PID setting level prohibited
Protect
*1
Not displayed on the Controller display.
*2
In 2-byte mode, the rightmost 16 bits are read.
*3
In 2-byte mode, the leftmost 16 bits are read.