![background image](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604101.webp)
5 - 7
5 Communications Data for Modbus
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
5
-1 V
ariab
le A
re
a (Setting
Rang
e) List
5
*1
The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently selected PID
set is fixed at PID1.
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
0A00
2A00
Proportional Band
*1
H'00000001 to H'0000270F (0.1 to 999.9)
0A02
2A01
Integral Time
*1
Standard, heating/cooling, or close position proportional control:
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
Floating position-proportional control:
H'00000001 to H'0000270F
(1 to 9999: Integral/derivative time unit is 1 s.)
(0.1 to 999.9: Integral/derivative time unit is 0.1 s.)
0A04
2A02
Derivative Time
*1
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
0A0A
2A05
MV Upper Limit
*1
Standard control or close position-proportional control:
MV lower limit + 0.1 to H'0000041A
(MV lower limit + 0.1 to 105.0)
Heating and cooling control:
H'00000000 to H'0000041A (0.0 to 105.0)
0A0C
2A06
MV Lower Limit
*1
Standard control or close position-proportional control:
H'FFFFFFCE to MV upper limit
−
0.1 (
−
5.0 to MV upper limit
−
0.1)
Heating and cooling control:
H'FFFFFBE6 to H'00000000 (
−
105.0 to 0.0)