3 - 23
3 Communications Data for CompoWay/F
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
3-1 V
ariab
le A
rea (Setting
Ran
g
e) List
3
*1
The set values for the program specified in the Program Selection parameter are accessed for the following
parameters: No. of Segments Used, Segment Selection, PID Set No., Alarm Values 1 to 4, Alarm Upper
Limits 1 to 4, Alarm Lower Limits 1 to 4, Program Repetitions, Program Link Destination No., Time Signal 1
and 2 Set Segments, Time Signal 1 and 2 ON Times, and Time Signal 1 and 2 OFF Times. Check the set
value of the Program Selection parameter before accessing these parameters.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C4 (84)
0014
Program
Repetitions
*1
H'00000000 to H'0000270F (0 to 9999)
Program
setting
C4 (84)
0015
Program Link
Destination No.
*1
H'FFFFFFFF (
−
1): No link
H'00000000 to H'00000007 (0 to 7)
C4 (84)
0016
Time Signal 1 Set
Segment
*1
Hí00000000 (0) to No. of segments used
−
1
C4 (84)
0017
Time Signal 1 ON
Time
*1
H'00000000 to H'00009959 (0.00 to 99.59) (hours,
minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes,
seconds)
C4 (84)
0018
Time Signal 1 OFF
Time
*1
H'00000000 to H'00009959 (0.00 to 99.59) (hours,
minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes,
seconds)
C4 (84)
0019
Time Signal 2 Set
Segment
*1
Hí00000000 (0) to No. of segments used
−
1
C4 (84)
001A
Time Signal 2 ON
Time
*1
H'00000000 to H'00009959 (0.00 to 99.59) (hours,
minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes,
seconds)
C4 (84)
001B
Time Signal 2 OFF
Time
*1
H'00000000 to H'00009959 (0.00 to 99.59) (hours,
minutes)
H'00000000 to H'00009959 (0.00 to 99.59) (minutes,
seconds)
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C5 (85)
0000
PID 1 Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
PID Setting
C5 (85)
0001
PID 1 Integral Time
Standard, heating/cooling, or close
position-proportional control: H'00000000 to
H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is
0.1 s.)
Floating position-proportional control:
H'00000001 to H'0000270F
(1 to 9999: Integral/derivative time unit is 1 s.)
(0.1 to 999.9: Integral/derivative time unit is
0.1 s.)
C5 (85)
0002
PID 1 Derivative Time
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is
0.1 s.)
C5 (85)
0003
PID 1 MV Upper Limit
Standard control or position proportional
(closed): MV lower limit +0.1 to H'0000041A
(MV lower limit +0.1 to 105.0)
Heating/cooling control: H'00000000 to
H'0000041A (0.0 to 105.0)