![Omron E5CC-T Communications Manual Download Page 104](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604104.webp)
5 Communications Data for Modbus
5 - 10
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
*1
Valid only with external communications.
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
0E14
2E0A
Event Input Assignment 1
H'00000000 (0): None
H'00000001 (1): RUN (OFF)/RESET (ON)
H'00000002 (2): RUN (ON)/RESET (OFF)
H'00000003 (3): Auto/Manual Switch
H'00000004 (4): RESET
H'00000005 (5): RUN
H'00000006 (6): Hold/clear hold
H'00000007 (7): Hold
H'00000008 (8): Advance
H'00000009 (9): Program No. switch 0
H'0000000A (10): Program No. switch 1
H'0000000B (11): Program No. switch 2
H'0000000C (12): Direct/reverse operation
H'0000000D (13): Program SP mode/fixed SP mode
H'0000001E (14): 100% AT execute/cancel
H'0000001F (15): 40% AT execute/cancel
H'00000010 (16): All PID 100% AT execute/cancel
H'00000011 (17): All PID 40% AT execute/cancel
H'00000012 (18): Setting Change Enable/Disable
H'00000013 (19): Communications Writing Enable/Disable
*1
H'00000014 (20): Alarm Latch Cancel
H'00000015 (21): Wait enable (ON)/Disable (OFF)
Initial setting
0E16
2E0B
Event Input Assignment 2
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
0E18
2E0C
Event Input Assignment 3
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
0E1A
2E0D
Event Input Assignment 4
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
0E1C
2E0E
Event Input Assignment 5
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
0E1E
2E0F
Event Input Assignment 6
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
0E20
2E10
Auxiliary Output 1
Assignment
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Program end output
H'0000000C (12): Stage output
H'0000000D (13): RUN output
H'0000000E (14): Time signal 1 output
H'0000000F (15): Time signal 2 output
H'00000010 (16): Integrated alarm
H'00000011 (17): Work bit 1
H'00000012 (18): Work bit 2
H'00000013 (19): Work bit 3
H'00000014 (20): Work bit 4
H'00000015 (21): Work bit 5
H'00000016 (22): Work bit 6
H'00000017 (23): Work bit 7
H'00000018 (24): Work bit 8
Advanced
function
setting
0E22
2E11
Auxiliary Output 2
Assignment
H'00000000 to H'00000018 (0 to 24)
Note: Same as for the Auxiliary Output 1 Assignment parameter.
0E24
2E12
Auxiliary Output 3
Assignment
H'00000000 to H'00000018 (0 to 24)
Note: Same as for the Auxiliary Output 1 Assignment parameter.
0E26
2E13
Auxiliary Output 4
Assignment
H'00000000 to H'00000018 (0 to 24)
Note: Same as for the Auxiliary Output 1 Assignment parameter.