3 - 17
3 Communications Data for CompoWay/F
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
3-1 V
ariab
le A
rea (Setting
Ran
g
e) List
3
C3 (83)
006F
Monitor/Setting
Item 2
H'00000000 to H'0000001E (0 to 30)
Note: Same as for Monitor/Setting Item 1.
Advanced
function
setting
C3 (83)
0070
Monitor/Setting
Item 3
H'00000000 to H'0000001E (0 to 30)
Note: Same as for Monitor/Setting Item 1.
C3 (83)
0071
Monitor/Setting
Item 4
H'00000000 to H'0000001E (0 to 30)
Note: Same as for Monitor/Setting Item 1.
C3 (83)
0072
Monitor/Setting
Item 5
H'00000000 to H'0000001E (0 to 30)
Note: Same as for Monitor/Setting Item 1.
C3 (83)
0073
PV/SP No. 1
Display Selection
H'00000000 (0): Nothing displayed.
H'00000001 (1): PV/SP
H'00000002 (2): PV
H'00000003 (3): SP/SP (character display)/Nothing
displayed
H'00000004 (4): PV/SP/MV (heating) (valve opening for
Position-proportional Models)
H'00000005 (5): PV/SP/MV (cooling)
H'00000006 (6): PV/SP/Program No. or segment No.
H'00000007 (7): PV/SP/Remaining segment time
C3 (83)
0076
PV Status Display
Function
H'00000000 (0): OFF
H'00000001 (1): Manual
H'00000002 (2): RESET
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Alarm 1 to 4 OR status
H'00000008 (8): Heater alarm
H'00000009 (9): Standby
C3 (83)
0077
SV Status Display
Function
H'00000000 to H'00000009 (0 to 9)
Note: Same as for PV Status Display Function
C3 (83)
0083
Display Refresh
Period
H'00000000 (0): OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
C3 (83)
0084
Alarm 4 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type. However,
the LBA (loop burnout alarm) cannot be set.
Initial
setting
C3 (83)
0085
Event Input
Assignment 5
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
C3 (83)
0086
Event Input
Assignment 6
H'00000000 to H'00000015 (0 to 21)
Note: Same as for Event Input Assignment 1.
C3 (83)
0087
Auxiliary Output 4
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function
setting
C3 (83)
0088
Alarm 4 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial
setting
Variable
type
Address
Parameter name
Setting (monitor) value
Level