This section describes the settings necessary to start component communications and the set point
calculations that are used to perform target point calculations at the slaves.
To perform component communications, change the parameter settings in the communications setting
level to the values that are given below.
*
Parameter details are the same as for programless communications. Refer to
.
Note: To use component communications, the input type and, if an analog input is used, the decimal point position
must be set to the same values for all of the E5
@
C-T/E5
@
C Controllers. The operation will not work correctly
if the position of the decimal point is different.
The parameters that are used for component communications are shown with a gray background in the
following diagram. All of these parameters are displayed if you set the Protocol Setting parameter to
cmp
. (Some of the parameters are always displayed.)
*
These parameters are displayed regardless of the setting of the Protocol Setting parameter.
Note: The Communications Data Length, Communications Stop Bits, and Communications Parity parameters in
the communications setting level are not displayed.
7-1-3
E5
@
C-T Controller Setup
Parameter
Set value
Master (E5
@
C-T)
Slaves (E5
@
C)
Protocol setting
CMP
CMP
Communications unit
number
0
A number is set for each slave in order
from 1.
Communications baud rate
57.6 (recommended)
57.6 (recommended)
Send data wait time
1 (recommended)
1 (recommended)
Highest communications
unit No.
Highest communications unit number of
all the slaves
Setting is not necessary
(The parameter is not displayed.)
M
M
M
M
M
Comm
u
nications
u
nit
N
o. = 0 (master)
Comm
u
nications
u
nit n
u
m
b
er
≠
0
(sla
v
e (Fixed-
v
al
u
e Controller)
M
M
M
M
M
M
25
0
psel
cmp
u-no
0
bps
57.6
sdwt
20
maxu
0
sps
1.000
spos
0.0
rwat
1000
l.adj
1234
at
off
cmwt
on
in-t
5
Initial Setting Le
v
el
Operation Le
v
el
Protocol Setting
*
Comm
u
nications
Unit
N
o.
*
Comm
u
nications
Ba
u
d Rate
*
Send Data
W
ait
Time
*
Highest
Comm
u
nications
Unit
N
o.
Recei
v
e Data
W
ait Time
Comm
u
nications Setting Le
v
el
Po
w
er O
N
SP Slope
SP Offset
Adj
u
stment Le
v
el
Display
AT Exec
u
te/Cancel
Comm
u
nications
W
riting
*
Adj
u
stment Le
v
el
Press
O
Key
for less than 1 s.
Press
O
Key
for less than 1 s.
Press
O
Key
for at least 3 s.
Press
O
Key
for at least 1 s.
Summary of Contents for E5CC-T
Page 2: ......
Page 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Page 185: ......