![Omron E5CC-T Communications Manual Download Page 80](http://html1.mh-extra.com/html/omron/e5cc-t/e5cc-t_communications-manual_742604080.webp)
3 Communications Data for CompoWay/F
3 - 34
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Status 2 Details
Note 1
“Spare” bits are always OFF.
2
When read in setup area 1, the status of the bits will be as follows:
Bit position
Status
Bit Description
0
1
Status
(lower
word)
0
Work bit 1
OFF
ON
1
Work bit 2
OFF
ON
2
Work bit 3
OFF
ON
3
Work bit 4
OFF
ON
4
Work bit 5
OFF
ON
5
Work bit 6
OFF
ON
6
Work bit 7
OFF
ON
7
Work bit 8
OFF
ON
8
Spare
OFF
---
9
Spare
OFF
---
10
Spare
OFF
---
11
Spare
OFF
---
12
Spare
OFF
---
13
Spare
OFF
---
14
Spare
OFF
---
15
Spare
OFF
---
Status
(upper
word)
16
Event input 5
OFF
ON
17
Event input 6
OFF
ON
18
Spare
OFF
---
19
Spare
OFF
---
20
Invert direct/reverse operation
Not invert
Invert
21
Spare
OFF
---
22
Spare
OFF
---
23
Spare
OFF
---
24
Time signal 1
OFF
ON
25
Time signal 2
OFF
ON
26
FSP Mode
OFF (PSP)
ON (FSP)
27
Spare
OFF
---
28
On standby
OFF
On standby
29
Ramp/soak
Soak
Ramp
30
Wait
OFF
Waiting
31
Hold
OFF
Holding
•
Work bits 1 to 8:
Cleared
•
Time signals 1 and 2:
Last value held
•
FSP Mode:
Last value held
•
On standby:
Last value held
•
Ramp/soak:
Last value held
•
Wait:
Last value held
•
Hold:
Last value held
Summary of Contents for E5CC-T
Page 2: ......
Page 184: ...Index 4 E5 C T Digital Temperature Controllers Programmable Type Communications Manual H186...
Page 185: ......