3 - 33
3 Communications Data for CompoWay/F
E5
C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
3
-2 Status a
nd Statu
s 2
3
Status Details
Note1
“Spare” bits are always OFF.
2
When read in setup area 1, the status of the bits will be as follows:
*
When the control output ON time is less than 30 ms for a control period of 0.1 s or 0.2 s or when it is less than
100 ms for any other control period, the bit is set to “1” and the heater current is held at the last current value.
Bit position
Status
Bit Description
0
1
Status
(lower
word)
0
Heater overcurrent (CT1)
Not generated
Generated
1
Heater current hold (CT1)*
Update
Hold
2
A/D converter error
Not generated
Generated
3
HS alarm (CT1)
OFF
ON
4
Spare
Not generated
---
5
Alarm 4
OFF
ON
6
Input error
Not generated
Generated
7
Potentiometer input error
Not generated
Generated
8
Control output (heating)/open output
OFF
ON
9
Control output (cooling)/close output
OFF
ON
10
HB (heater burnout) alarm (CT1)
OFF
ON
11
HB (heater burnout) alarm (CT2)
OFF
ON
12
Alarm 1
OFF
ON
13
Alarm 2
OFF
ON
14
Alarm 3
OFF
ON
15
Program end output
OFF
ON
Status
(upper
word)
16
Event input 1
OFF
ON
17
Event input 2
OFF
ON
18
Event input 3
OFF
ON
19
Event input 4
OFF
ON
20
Write mode
Backup mode
RAM write mode
21
Non-volatile memory
RAM = Non-volatile
memory
RAM
≠
Non-volatile
memory
22
Setup area
Setup area 0
Setup area 1
23
AT execute/cancel
AT canceled
AT execution in
progress
24
RUN/RESET
Run
Reset
25
Communications writing
OFF (disabled)
ON (enabled)
26
Auto/manual switch
Automatic mode
Manual mode
27
Spare
OFF
---
28
Heater overcurrent (CT2)
Not generated
Generated
29
Heater current hold (CT2)
Update
Hold
30
Spare
OFF
---
31
HS alarm (CT2)
OFF
ON
•
Overcurrent: Last
value
held
•
A/D converter error:
Last value held
•
Input error:
Last value held
•
Potentiometer input error
Last value held
•
HB and HS outputs:
Cleared
•
Program end output:
Cleared
•
Current hold:
Last value held
•
Heating and cooling outputs,
open output, close output
Cleared
•
Alarm outputs:
Cleared