5
Address
Parameter name
Setting (monitor) value
Level
4 bytes
2 bytes
1500
3500
PID 1 Proportional Band
H'00000001 to H'0000270F (0.1 to 999.9)
PID Setting
1502
3501
PID 1 Integral Time
Standard, heating/cooling, or close position-proportional control:
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
Floating position-proportional control: H'00000001 to H'0000270F
(1 to 9999: Integral/derivative time unit is 1 s.)
(0.1 to 999.9: Integral/derivative time unit is 0.1 s.)
1504
3502
PID 1 Derivative Time
H'00000000 to H'0000270F
1506
3503
PID 1 MV Upper Limit
Standard control or close position-proportional control:
MV lower limit + 0.1 to H'0000041A
(MV lower limit + 0.1 to 105.0)
Heating/cooling control: H'00000000 to H'0000041A (0.0 to 105.0)
1508
3504
PID 1 MV Lower Limit
Standard control or close position-proportional control:
H'FFFFFFCE to MV upper limit
−
0.1
(
−
5.0 to MV upper limit
−
0.1)
Heating/cooling control: H'FFFFFBE6 to H'00000000 (
−
105.0 to 0.0)
150A
3505
PID 1 Automatic
Selection Range Upper
Limit
Temperature input: H'FFFFF831 to H'0000270F (
−
1999 to 9999)
Analog input: H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
150E
3507
PID 1 LBA Detection
Time
H'00000000 to H'0000270F (0 to 9999)
1510
3508
PID 1 Proportional Band
(Cooling)
H'00000001 to H'0000270F
1512
3509
PID 1 Integral Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
1514
350A
PID 1 Derivative Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
1516
350B
PID 1 Dead Band
Temperature input: H'FFFFF831 to H'0000270F (
−
1999 to 999.9)
Analog input: H'FFFFF831 to H'0000270F (
−
199.9 to 999.9)
1518
350C
PID 1 Manual Reset
Value
H'00000000 to H'000003E8 (0.0 to 100.0)
1520
3510
PID 2 Proportional Band
Temperature input: H'00000001 to H'0000270F (0.1 to 999.9)
Analog input: H'00000001 to H'0000270F (0.1 to 999.9)
to
1538
351C
PID 2 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
1540
3520
PID 3 Proportional Band
Temperature input: H'00000001 to H'0000270F (0.1 to 999.9)
Analog input: H'00000001 to H'0000270F (0.1 to 999.9)
to
1558
352C
PID 3 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
1560
3530
PID 4 Proportional Band
Temperature input: H'00000001 to H'0000270F (0.1 to 999.9)
Analog input: H'00000001 to H'0000270F (0.1 to 999.9)
to
1578
353C
PID 4 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
1580
3540
PID 5 Proportional Band
Temperature input: H'00000001 to H'0000270F (0.1 to 999.9)
Analog input: H'00000001 to H'0000270F (0.1 to 999.9)
to
1598
354C
PID 5 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
15A0
3550
PID 6 Proportional Band
Temperature input: H'00000001 to H'0000270F (0.1 to 999.9)
Analog input: H'00000001 to H'0000270F (0.1 to 999.9)
to
15B8
355C
PID 6 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)
15C0
3560
PID 7 Proportional Band
Temperature input: H'00000001 to H'0000270F (0.1 to 999.9)
Analog input: H'00000001 to H'0000270F (0.1 to 999.9)
to
15D8
356C
PID 7 Manual Reset
Value
H'00000000 to H'0000270F (0 to 9999)